Checking The Usage; Part Designations; Type Label; Installation - Honeywell Krom Schroder DG H Series Operating Instructions Manual

Pressure switches for gas
Table of Contents

Advertisement

Checking the usage

DG..H, DG..N, DG..I
For monitoring increasing and decreasing gas or
air pressure.
Increasing
negative pressure
Decreasing
negative pressure
-6 -5 -4 -3 -2 -1 0 1
Positive pressure
DG..H,
Gas, air, flue gas Air, flue gas
DG..N
DG..I
Air, flue gas
DG..H switches and locks off with rising pressure,
DG..N switches and locks off with falling pressure.
They can be unlocked using the manual reset.
This function is only guaranteed when used within
the specified limits – see page 7 (Technical data).
Any other use is considered as non-compliant.
Type code
Code
DG
1,5 – 500
Locks off with rising pressure
H
N
Locks off with falling pressure
I
G
-
-4
-5
-6
-9
4-pin plug, with socket, IP 65
K
Red/green pilot LED for 24 V DC/AC
T
Blue pilot lamp for 230 V AC
T
Red/green pilot LED for 230 V AC
N
Blue pilot lamp for 120 V AC
A

Part designations

2
1
1
Upper housing section with cover
Lower housing section
Hand wheel
4
M16 cable gland
5
DG..H, DG..N with manual reset
Increasing pressure
Decreasing pressure
2
3
4
5
6
Negative pressure
Gas, air, flue gas
Description
Pressure switch for gas
Max. setting in mbar
Negative pressure for gas
With gold-plated contacts
Electrical connection
via screw terminals
via screw terminals, IP 65
4-pin plug, without socket
4-pin plug, with socket
External adjustment
5
3
4

Type label

D-49018 Osnabrück, Germany
DG
CE
Max. inlet pressure p
voltage, ambient temperature, enclosure: see type
label.

Installation

CAUTION
Please observe the following to ensure that the DG
is not damaged during installation and operation:
Continuous operation with gases containing more
than 0.1 %-by-vol. H
exceeding 200 µg/m³ accelerate the ageing of
elastomer materials and reduce the service life.
Dropping the device can cause permanent dam-
age. In this event, replace the entire device and
associated modules before use.
Use approved sealing material only.
Check max. ambient temperature  – see
page 7 (Technical data).
When using silicone tubes, only use silicone
tubes which have been sufficiently cured.
Vapours containing silicone can adversely affect
the functioning of electrical contacts.
Condensation must not be allowed to get into
the housing. At subzero temperatures, malfunc-
tions/failures due to icing can occur.
When installing outdoors, place the DG in a
roofed area and protect from direct sunlight
(even IP 65 version). To avoid condensation, a
cover with pressure equalization element (see
page 6 (Pressure equalization element)) can
be used.
Avoid strong impact on the unit.
In case of highly fluctuating pressures, install
a restrictor orifice (see page 6 (Restrictor
orifice)).
▷ The DG must not be in contact with masonry.
Minimum clearance 20 mm.
▷ Ensure that there is sufficient installation space.
▷ Ensure unobstructed view of the hand wheel.
▷ Installation position as required, preferably with
vertical diaphragm. Then the switching point p
corresponds to the scale value SK set on the
hand wheel. In other installation positions, the
switching point p
correspond to the scale value SK set on the
hand wheel. Check the switching point.
GB-2
2
3
1
= withstand pressure, mains
max.
S or ozone concentrations
2
will change and no longer
S
S

Advertisement

Table of Contents
loading

This manual is also suitable for:

Krom schroder dg n seriesKrom schroder dg i seriesKrom schroder dg 10hKrom schroder dg 10nKrom schroder dg 50hKrom schroder dg 50n ... Show all

Table of Contents