2.3. POWER SUPPLY
Profibus-DP Bus
The Power supply is provided by the X0 connector, which is also used to link data between the Profibus-DP
interface card and the drive regulation card.
The PDP card requires 24Vdc at 350mA.
2.4. CONNECTORS
Connector PEG:
It allows to connect set point of External Digital Supply (GNDE) to the ground (PE).
Connector PES:
It allows to connect the ground (PE) at the Profibus cables shield.
2.5. DIP SWITCHES
s3
s4
s5
S6
s7
SS
s9
SlO
2.6. LEDS
+5v
RST
DEA
+5VE
Selection of interrupt source (INTl / INT2) from S5 jumper to the 8032 microcontroller
or the Dual Port Ram interrupt input (INTR). Default position A (interrupt from the
Dual Port Ram).
i
Synchronization connection of the 6KCV300PDPBl card reset signal to the drive
regulation card reset signal. Default positiont ON.
It is used to connect the m-OPZ
signal to the INTl signal (S5 A) or to the INT2 signal
(S5 B). At the moment only the setting (default setting) of the interface card as Option 1
is allowed, therefore INT_OPZ is connected to the WI'1 signal (default position A).
It is used to connect the OUT-OPZ signal to the OUT1 (S6.A) or OUT2 (S6.B) signal.
Default position A.
It is used to connect the CEM-OPZ signal to the OPZl (S7.A) or OPZ2 (S7.B) signal.
The default setting of the 6KCV300PDPB 1 card is Option 1, therefore the CEM-OPZ
signal is connected to the OPZl signal. (Default position A).
Connection of the Dual Port Ram BUSY signal to RDY-EXT signal. Default position ON.
It is used for ibrid connection for communication. It allows to connect the capacitor C3
(1OnF 2kV) in case the connection is too long.
It is used for ibrid connection of the ground. It allows to connect the capacitor C4 (10nF
2kV) in case the connection is too long.
+5V power supply.
Reset active.
Data Exchange Phase active.
+5V power supply on the RS 485 driver side galvanic isolated.
HARDWAfRE DESCRIPTION