8-degree Mesh Patch Panel with 5 Add/Drop Ports (NCS2K-PPMESH8-5AD=)
Figure 25: 19-inch brackets with 7.6" and 9.2" recess location for EIA standard racks
The following figure shows 39 mm recess location for ETSI standard racks.
Figure 26: ETSI brackets with 39 mm recess location for ETSI standard racks
The following figure shows 55 mm recess location for IEC standard racks.
Figure 27: 19-inch brackets with 55 mm recess location for IEC standard racks
Caution
Use only the fastening hardware provided with the 8-degree mesh patch panel to prevent loosening,
deterioration, and electromechanical corrosion of the hardware and joined material.
Caution
When mounting the 8-degree mesh patch panel in a frame with a non-conductive coating (such as paint,
lacquer, or enamel) use either the thread-forming screws provided with the shipping kit or remove the coating
from the threads to ensure electrical continuity.
Note
It is recommended to configure the PPMESH8-5AD passive modules after configuring the other passive
modules. If any passive modules are configured after the PPMESH8-5AD module, the snmpwalk operation
ends without incrementing the error message OID. The checking of OID order must be disabled in SNMP
manager to avoid this error. For example, issue the following command from net-snmp: ./snmpwalk -v2c -c
public -Cc IP address .1
This procedure describes the steps to install the 8-degree mesh patch panel module.
Procedure
Step 1
Mount the brackets on the patch panel (see the Figure 29):
Installing the Cisco NCS 2000 Series Passive Optical Modules
28
Installing the Cisco NCS 2000 Series Passive Optical Modules