CHAPTER 6: SPECIFICATIONS

Altitude

Ingress Protection (IEC 60529)

Liquid Protection

Mean Time Between Failure

G500 SUBSTATION GATEWAY INSTRUCTION MANUAL
These tests were conducted with all interfaces loaded at typical load conditions.
Maximum operating altitude is 2000m.
Above this altitude the isolation requirements for substations (IEC61010-1) couldn't be
guaranteed. Thermal de-rating due to altitude is characterized in the table below:
Altitude
2500m
3000m
IP30 (protected from tools and wires greater than 2.5 millimeters).
The G500 is designed to protect the internal electronics from small amounts of liquid
falling vertically or which may accumulate on the top surface of the chassis.
Part
MCP Core System
G500 System 4 Core* 16GB, 8 Serial ports,
w/o PSU
Power Supplies
HV PSU
LV PSU
PCIe add in cards
4 port Serial PCIe card
SFP Modules, Max 6 combined types
SFP Module 100/1000BASE-T RJ45 TRANS-
CEIVER COPPER
SFP Module 100BASE-FX LC TRANSCEIVER
OPTICAL
SFP Module 1000BASE-SX LC TRANS-
CEIVER OPTICAL
G500 System 2 Core 8GB, 8 serial ports without PSU has slightly higher MTBF.
GE INFORMATION
Temperature de-rating
5°C
10°C
GE Part
Failure In
Number
Time (FIT)
528-0002LF*
15779.6
(528-0001LF)
528-2001LF
3830.5
528-2002LF
3567.0
528-1001LF
2911.2
580-3786
134.8
580-3784
228.2
580-3785
164.0
MTBF in hours
@40°C
63373
261062
280347
343498
7417297
4382121
6097561
75