Control Parameters Of The Load Controller; Selection Of The Standard Parameter Set; Individual Setting Of The Pid Parameters; Automatic Adaption - Siemens LMV51 Series Basic Documentation

Burner control with integrated fuel / air ratio control and load control, load control including o2 trim control for forced draft burners
Hide thumbs Also See for LMV51 Series:
Table of Contents

Advertisement

1. Selection of the
standard parameter set
2. Individual setting of
the PID parameters
Menu level 1
Params & Display

3. Automatic adaption

Menu level 1
Params & Display
166/301
Siemens Building Technologies
HVAC Products

8.1.6 Control parameters of the load controller

The control parameters can be defined in 3 different ways.
The memory of the load controller contains 5 standard parameter sets.
Depending on the characteristics of the controlled system, a PID triple value can be se-
lected and activated.
The following standard parameter sets can be chosen:
Very fast
Fast
Normal
Slow
Very slow
Alternatively, the PID parameters can be directly selected and set within the predefined
value range.
Menu level 2
Menu level 3
LoadController
ControllerParam
Or
With the method of adapting the control parameters, the characteristic data of the con-
trolled system are acquired with an adaption procedure whereupon matching PID pa-
rameters will be calculated.
If possible, the adaption load should be 100 %.
Menu level 2
Menu level 3
LoadController
Adaption
Basic Documentation LMV5...
8 Commissioning instructions for the LMV5... system
P [%]
I [s]
40
55
4
35
7
90
15
320
30
400
Menu level 4
Menu level 5
ContrlParamList
StandardParam
P-Part (Xp)
I_Part (Tn)
D-Part (Tv)
Menu level 4
Menu level 5
StartAdaption
AdaptionLoad
D [s]
15
17
50
40
10
Menu level 6
Adaption
very fast
fast
normal
slow
very slow
Menu level 6
CC1P7550en
13.08.2004