Settings For Multistage Firing On Oil; Fuel Changeover For Firing On Oil; Changing The Burner Operating Mode From Modulating To Multistage (Only When Firing On Oil); Activating The Program Stops In The Different Program Phases - Siemens LMV51 Series Basic Documentation

Burner control with integrated fuel / air ratio control and load control, load control including o2 trim control for forced draft burners
Hide thumbs Also See for LMV51 Series:
Table of Contents

Advertisement

18. Fuel changeover
for firing on oil
Menu level 1
Operation
19. Changing the burner
operating mode from
modulating to multistage
(only when firing on oil)
Menu level 1
Params & Display
20. Activating the
program stops in the
different program phases
Menu level 1
Menu level 2
Params & Display
RatioControl
158/301
Siemens Building Technologies
HVAC Products

8.1.3 Settings for multistage firing on oil

Fuel changeover on the AZL5... is possible only if input «FuelSelect» is set to «internal».
Set fuel selection to «Oil» or set the external fuel selector to «Oil».
Menu level 2
Menu level 3
Fuel
FuelSelect
Here, the burner operating mode can be set to «2-stage» or «3-stage».
Menu level 2
Menu level 3
RatioControl
OilSettings
Activate the program stop if startup shall be interrupted to continue setting the special
positions.
Prepurge
Ignition position
Interval 1
Interval 2
Postpurge
Menu level 3
ProgramStop
Activate a program stop in Phase 24.
Basic Documentation LMV5...
8 Commissioning instructions for the LMV5... system
Menu level 4
Menu level 4
CurveParams
Phases 24 - 34
Phase 36
Phase 44
Phase 52
Phases 72 - 78
Menu level 4
deactivated
24PrePurgP
32PreP FGR
36IgnitPos
44Interv1
52Interv2
72PostPPos
76PostPFGR
Menu level 5
Menu level 6
Menu level 5
Menu level 6
Operation Mode
Menu level 5
Menu level 6
CC1P7550en