21. Checking and
presetting the ignition
positions for firing on oil
Menu level 1
Menu level 2
Params & Display
RatioControl

22. Manual startup

Menu level 1
ManualOperation
23. Actuator positions
during the prepurge time
Menu level 1
Menu level 2
Params & Display
RatioControl

Note:

Siemens Building Technologies
HVAC Products
For the parameters «home, prepurge and postpurge position», the parameter set as sup-
plied contains presettings. These should be checked and, if necessary, adapted, either
now or during the following program stops.
There is no presetting for the ignition position. In this section, a valid setting must be
made because otherwise, the burner cannot be started up.
Menu level 3
OilSettings
Gas actuator: 22.5°
Example:
These values are also transferred to operating point S1 even if it has not yet been set.
To start the burner, select «Autom/Manual/Off» to choose «BurnerOn».
Menu level 2
Menu level 3
Autom/Manual/Off
If startup shall be watched, the display can be changed to «Normal operation» by
pressing simultaneously selection buttons «<» and «>».
The burner control stops startup in the prepurge phase (Phase 24), so that the posi-
tions of the actuators for prepurging can be straightforwardly set.
Menu level 3
OilSettings
The prepurge position of auxiliary actuator 3 is approached in Phase 32 (FGR).
After the settings are made, the program stop in the prepurge position should be re-
placed by the program stop of the ignition position in Phase 36.
Basic Documentation LMV5...
8 Commissioning instructions for the LMV5... system
Menu level 4
Menu level 5
SpecialPositions
IgnitionPos
Air actuator: 37.6°
Menu level 4
Menu level 4
Menu level 5
SpecialPositions
PrepurgePos
Menu level 6
IgnitionPosOil
IgnitionPosAir
IgnitionPosAux
Aux2
Aux3
VSD
Menu level 5
Menu level 6
Menu level 6
PrepurgePosAir
PrepurgePosAux
Aux2
Aux3
VSD
Only
LMV52...
Only
LMV52...
159/301
CC1P7550en
13.08.2004

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents