Honeywell FlexLine SmartServo 954 Service Manual page 181

Servo-based level gauge
Hide thumbs Also See for FlexLine SmartServo 954:
Table of Contents

Advertisement

COMMISSIONING
Part No.: 4417340 Revision 1
30 till 59 for the second FCM- TRL/2 Module
60 till 99 for the third FCM- TRL/2 Module
FlexConn instrument start address:
FlexConn instrument stop address:
When one FCM- TRL/2 Module is used in the SmartLink, the default
start and stop addresses can be used.
When two or three FCM- TRL/2 Modules are used in the SmartLink, a
division must be made, like described above.
NOTE: This is only required when FlexConn gauges are connected
(like the 954 SmartServo FlexLine).
Time-out GPU instrument reply:
A time-out can be specified on the instrument's reply record. The time-
out can be set between 10 and 2000 msec.
Password:
Refer to the password description of the HCM-GPU module.
Function identification:
In the SmartLink, the FCM- TRL/2 module has the function of: TRL/2-
master (the instrument is the TRL/2- slave).
Service Manual
954 SmartServo FlexLine
173