6.6 TRLYS1D Relay Output with Solenoid Integrity
Sensing
The Relay Output with Solenoid Integrity Sensing (TRLYS1D) terminal board holds six plug-in magnetic relays. The six
relay circuits are Form-C contact outputs, powered and fused to drive external solenoids. A standard 24 V dc or 125 V dc
source can be used. The board provides special feedback on each relay circuit to detect a bad external solenoid. Sensing is
applied between the NO output terminal and the SOL output terminal.
TRLYS1D is similar to the standard TRLYS1B board except for the following:
There are six relays.
The board is designed for 24/125 V dc applications only.
Relay circuits have a NO contact in the return side as well as the source side.
The relays cannot be configured for dry contact use.
Input relay coil monitoring is removed.
The terminal board provides monitoring of field solenoid integrity.
There is no special-use relay for driving an ignition transformer.