Setup RF Channel
Figure 8. Setup RF Channel
1. After rF is displayed, press MODE.
2. Default rF value 26 displayed on the screen.
3. Use the UP/DOWN arrows to change value
range between 11 to 26.
4. Press FAN, the unit beeps to confirm the
value stored in the memory and display will
be back rF.
5. Press MODE to check the value.
6. Once the rF configured, Press FC to re-
turn INTIALIZATION MODE.
7. If you want to continue, press the DOWN ar-
row button to display PAn mode
Or
If you want to exit the INTIALIZATION MODE,
press the FC key.
After you configured RF channel, you need to
configure PAN channel for IRAS communica-
tion.
Figure 9. Configuring RF channel
e7w WIRELESS EMS THERMOSTAT - INSTALLATION INSTRUCTIONS
Setup PAn ID
After PAn is displayed, press MODE.
1. Default PAn value is 0 displayed on the
screen.
2. Use the UP/DOWN arrows to change value
range between 0 to 255.
3. Press FAN, the unit beeps to confirm the
value stored in the memory, the display will
be back to PAn.
4. Press MODE to check the value.
8. Once the PAn configured, Press FC to re-
turn INTIALIZATION MODE.
9. If you want to continue, press the DOWN ar-
row button to display rld mode
Or
If you want to exit the INTIALIZATION MODE,
press the FC key.
Service Mode
To configure the HVAC controller, wireless mo-
tion
sensors,
switches with e7w, you need to set e7w into Ser-
vice Mode.
To enter Service, follow the below steps:
1. Press and hold FC key.
2. Press and release MODE.
3. Press and release FAN.
4. Release FC key.