Description & Commissioning
How to check S-Quad Exception codes
The Exception codes are also sometimes called condition codes and these codes provide information about a sensor device. A code
indicates small changes in the:
¨
environmental condition
¨
sensor mechanism and
¨
how the sensor performs in the system.
"
To ensure that the sensor exception codes are meaningful, after power up the system should be left
undisturbed for at least 24 hours.
Definition
There are ten different conditions possible for each sensor type, although not all of them are defined. Each condition code has a
range of 0-3,
Exception/
Meaning
Condition Code
0
This condition is OK. This code is not displayed unless another non zero code exists.
1 or 2
Suggest preventive maintenance is required, where necessary, to avoid possible false alarms.
3
The sensor is faulty. A fault condition indication is given at the control panel. A message
reading 'Sensor Out of Specification' is displayed.
"
A sensor having code 3 is automatically disabled by the system to prevent false alarms.
To view the exceptions/condition codes of a device/outstation:
Press Menu On/Off button
a.
Select [Info] and press <etc> to select [Event]
b.
Press <etc> and select [Exception] and then select [Enter].
c.
Time and date when exceptions (Conditon code /Subfault) were read
Time: 15:54.07
Exception
Number 2 on Loop 1
condition
3
1
These are position numbers as they appears
in the exceptions (or condition code) table.
8
Wed 20 June 2012
3
3
3
3
3
3
3
2
3
4
5
6
7
8
23:15
3
3
9
10
Device number residing on loop
number stated here whose
exceptions are shown
These exceptions/condition codes
indicate the device is probably
disconnected