8.5.6 LCD Function

Testing the LCD hardware. Back-light is active for about 2 secs. The backlight is yellow. (Green and red are
activated at the same time). All segments are active on LCD.
Installation &
Calibration
The following area is only accessible if the service is set to "ON".
With code priority 4 for reading the parameters
With code priority 1 or 3 for changing the parameters.

8.6 Menu Relay Parameters

Reading and changing of the parameters separately for each alarm relay.
Relay Parameters

8.6.1 Relay Mode

The fault relay is listed as relay 3 and can be registered here as an
additional alarm relay. This registration has no influence on the
function as fault relay.
The relay switches off in addition when the assigned alarm is
active.
Symbol
Description
Used
Mode

8.6.2 Relay Operation Mode

Relay 3:
The parameter setting "Energized" cannot be changed.
The terms energized / de-energized come from the terms "energized / de-energized to trip" principle used for
safety circuits. The terms refer to the activation of the relay coil, not to the relay contacts (as they are executed
as changeover contacts and available in both principles).
The LEDs at the modules show the state in analogy. (LED off -> relay coil current-free)
Symbol
Description
De-
Mode
energ.
®
PolyGard
is a registered trademark of MSR
Phone 0049(0)8531/9004-0
Fax: 0049(0)8531/9004-54
MSR-Electronic GmbH, Bgm.-Schoenbauer-Str. 13, D 94060 Pocking www:msr-electronic.de Made in Germany
®
2
LCD Function
check?
Service
OFF
Relay
Used
Selection of alarm relay 1 - 5
Default
Function
Used
Used
Not Used
Default
Function
De-energ.
= Alarm OFF= Relay (and LED) current-free
Alarm ON = Relay (and LED) energized
De-
energ.
Energ.
= Alarm OFF = Relay (and LED) permanently energized
Alarm ON = Relay (and LED) current-free
1
Relay Mode
Used
= Relay is registered and can be assigned to
an alarm
= Relay isn't registered
Operation Mode
Energized
Specification subject to change without notice
Page
16
GAMGC2-K_E_0320