Dimensions
Height (H) = 50mm (108mm including plug and lead)
Width (W) = 315mm (361mm including mounting feet)
Depth (D) = 205mm
Fixing Centres (F) = 340mm
Technical Data
Operational Supply: 230V ~ 50Hz
Power Consumption: 18W maximum
Product Rating & Recommended Circuit Protection: 16A
Max Switched Live Load per Channel: 6A
Max Total Switched Live Load: 16A
Digital Dimming Ballasts per Channel: 10 maximum
Digital Dimming Ballasts per LCM: 40 maximum
1-10V Dimming Ballasts per Channel: 20mA (SINKING only). See manufacturer's
specification: worst case 10 ballasts but Philips HF-R, for example, 20 ballasts.
Observe Switched Live Load limits above.
Maintained Live Output: 2A total per LCM
Mains Supply Terminal Capacity: 1x2.5mm² or 1x4.0mm²
Override Switch Input Connector: 2.5mm²
MLS Bus Connector: 2.5mm²
MLS Bus Cable: 1.5mm² unscreened twisted pair - see Application Note AN4001
Case Material: Polycarbonate
Case Finish: Lightly textured charcoal grey RAL7016
Part Numbers
CDW12U5
Programmable LCM with 12 luminaire sockets, 5 sensor
and 5 override sockets
CDW12U5-B
with MLS Bus operation card
CDW12U5-A
c/w Analogue 1-10V dimming
CDW12U5-BA
with MLS Bus card c/w Analogue 1-10V dimming
CDW12U5-BAWL
with MLS Bus card and wireless switch card
CDW12U5-DALI
c/w Digital DALI dimming
CDW12U5-BDALI
with MLS Bus card c/w Digital DALI dimming
CDW12U5-BDALIWL
with MLS Bus card & wireless switch card c/w Digital DALI dimming
CDW12U5-D
c/w DSI dimming
CDW12U5-BD
with MLS Bus operation card c/w Digital DSI dimming
CDW12U5-BDWL
with MLS Bus & wireless switch card c/w Digital DSI dimming
CDWDC
Plug-in Digital Dimming Card
CDWAC
Plug-in Analogue Dimming Card
CDWBC
Replacement MLS Bus Interface
Sensors with photocell:
MLS2500CDR
Corner-mount Microwave, semi-flush mounted
MLS2500CDRSM
As above - surface mounted
MLS2401CDR
360° Microwave, flush mounted
MLS2401CDRSM
As above - surface mounted
MLS3000CDRF
360° PIR, flush mounted
MLS300CDRSM
As above - surface mounted
MLS3003CDRF
360° PIR with tilting lens, flush mounted
MLS3003CDRSM
As above - surface mounted
MLS3003CDRMBF
360° Mid-Bay PIR with tilting lens, flush mounted
MLS3003CDRMBSM
As above - surface mounted
MLS3003CDRHBF
360° Hi-Bay PIR with tilting lens, flush mounted
MLS3003CDRHBSM
As above - surface mounted
MLSM2002CDR
Control module for integration within luminaire
DHS
360° Mini detector head for use with MLSM2002CDR - silver bezel
DHW
360° Mini detector head for use with MLSM2002CDR - white bezel
MLSM2002CDRDHPBW Mini Detector c/w Control Module & Plasterboard Mounting Kit
Sensor Patch Leads:
BT5E030GY
3m Patch Lead
BT5E050GY
5m Patch Lead
BT5E100GY
10m Patch Lead
Luminaire Leads:
CPWL633
3m, 3-core, 6-pole GST 18/6 Plug & Ex-Or Latching Shell
CPWL635
5m, 3-core, 6-pole GST 18/6 Plug & Ex-Or Latching Shell
CPWL653
3m, 5-core, 6-pole GST 18/6 Plug & Ex-Or Latching Shell
CPWL655
5m, 5-core, 6-pole GST 18/6 Plug & Ex-Or Latching Shell
CPWL663MF
3m Luminaire Extenstion Cable - 6-pole, 6-core male/female GST 18/6
Emergency Luminaire Leads:
CPWL643
3m, 4-core, 6-pole GST 18/6 Plug & Ex-Or Latching Shell
CPWL645
5m, 4-core, 6-pole GST 18/6 Plug & Ex-Or Latching Shell
CPWL663
3m, 6-core, 6-pole GST 18/6 Plug & Ex-Or Latching Shell
CPWL665
5m, 6-core, 6-pole GST 18/6 Plug & Ex-Or Latching Shell
Plugs
CPWL6
GST18/6 Plug & Ex-Or Latching Shell
CPWL6S
GST-6 Ex-Or Plug-locking mechanism (shell only)
CDWIP
Switch Input Plugs (set of 5)
Honeywell Ex-Or
St. Marks Court, North Street, Horsham, West Sussex, RH12 1BW, UK.
Tel: +44 (0)1942 719229, Fax: +44 (0)1942 508753
Email: technicalsales.ex-or@.com
www.ex-or.com
W
D
2
F
Weight = 1.55 kg
An Example Configuration
A school classroom, where a sophisticated blend of manual and automatic control is
required, with overall manual control by staff augmented by automatic dimming control of
luminaires adjacent to large windows and the automatic switch-off of the lights following an
often ragged quitting of the room at the end of a teaching session, where staff typically will
not be the last to leave.
H
Sensor
SW1
SW2
SW3
Important Additional Notes
1.
The CDW12U5 must be earthed as it provides the only path to earth for luminaires
connected through it.
2.
A dimming control output should be connected only to the control inputs of ballasts,
never to another channel's dimming output and never to other types of equipment.
3.
Although nominally 12V, the dimming control outputs are not to be treated as SELV,
due to their passage through multiple luminaire enclosures and therefore should be
treated with the same respect as mains with regard to wiring practice.
4.
This equipment switches lights no more frequently than would a responsible human
occupant. However, manufacturers of some particular lighting types (e.g. '2D'
luminaires) may specify a maximum number of switching cycles and/or a minimum
on-time in order to achieve a predicted lamp life. Please check with the
manufacturer of the luminaires to ensure that they are compatible with automatic
controls in this respect.
Ex-Or operates a genuine policy of continuous improvement. You may expect the specification to
be regularly enhanced. For the latest technical information please visit www.ex-or.com
At the end of their useful life
the packaging and product
should be disposed of via a
suitable recycling centre.
Do not dispose of with
normal household waste.
Do not burn.
SW1 SW2
Sensor
, (All Channels, 1-6)
, (Channels 4 & 5)
1
2
3
, (Channels 2 & 4)
, (Channels 1, 2 & 6)
, (Channel 3)
W4400O

Advertisement

loading