1MRS756878 H
0xA
CS
2068
2.08
2069
2.09
2070
2.10
2071
2.11
2072
2.12
2073
2.13
2074
2.14
2075
2.15
2076
3.14
2.5.2
Table 166:

CTRL.CBCSWI1 Circuit breaker control (1)

0xA
CS
2048
1.00
2049
1.01
2050
1.02
2051
1.03
2052
1.04
2053
1.05
2.5.3
Table 167:

CTRL.DCXSWI1 Disconnector control (1)

0xA
CS
2144
7.00
2145
7.01
2146
7.02
Table continues on next page
RET615
Point List Manual
IEC 61850 name
.MemClr.Oper.ctlVal
LD0.CMMXU1
.RecRs.Oper.ctlVal
LD0.PEMMXU1
.SupDmdRs.Oper.ctlVal
LD0.SCCBR1
.RsTrvTm.Oper.ctlVal
.RsSprChaTm.Oper.ctlV
al
LD0.RESCMMXU1
.RecRs.Oper.ctlVal
LD0.RESVMMXU1
.RecRs.Oper.ctlVal
LD0.CMMXU2
.RecRs.Oper.ctlVal
LD0.RESCMMXU2
.RecRs.Oper.ctlVal
CTRL.CBCSWI1 Circuit breaker control (1)
IEC 61850 name
CTRL.CBCSWI1
.Pos.Oper.ctlVal
.Pos.Oper.ctlVal
.Pos.Oper.ctlVal
.Pos.Oper.ctlVal
.Pos.Oper.ctlVal
.Pos.Oper.ctlVal
CTRL.DCXSWI1 Disconnector control (1)
IEC 61850 name
CTRL.DCCSWI1
.Pos.Oper.ctlVal
.Pos.Oper.ctlVal
.Pos.Oper.ctlVal
SA name
Description
Clear DR memory
Reset max current1 demands
Reset energy values
Reset CB travel time
Reset CB spring charge time
Reset Io (1) max demands
Reset Uo (1) max demands
Reset max current2 demands
Reset Io (2) max demands
SA name
Description
Select open
Select close
Cancel selection
Execute selection
Direct open
Direct close
SA name
Description
Select open
Select close
Cancel selection
Section 2
Modbus data mappings
Values
1=Clear
1=Reset
1=Reset
1=Reset
1=Reset
1=Reset
1=Reset
1=Reset
1=Reset
Values
1=Select
1=Select
1=Cancel
1=Execute
1=Open
1=Close
Values
1=Select
1=Select
1=Cancel
85