Section 2
Modbus data mappings
2.4.2.1
Table 155:

CTRL.LLN0 Local, Remote, Station, Off and Combinations

RegA
Type
u16
2.4.2.2
Table 156:

LD0.FMMXU1 Frequency measurement (1)

RegA
Type
Scale
u16
100
2.4.2.3
Table 157:

LD0.LLN0/LPHD1/LDEV1 System values

RegA
Type
Scale
u16
1
2.4.2.4
Table 158:

LD0.MDSOPT1 Runtime counter for machines and devices (1)

RegA
Type
u16
2.4.2.5
Table 159:

LD0.MVI4GAPC1 Integer value move (1)

RegA
Type
i32
Table continues on next page
82
little meaning, since it is always possible to redefine the settings completely for the
user-definable register.
CTRL.LLN0 Local, Remote, Station, Off and Combinations
Scale
IEC 61850 name
CTRL.LLN0
1
.LocKeyHMI.stVal
LD0.FMMXU1 Frequency measurement (1)
IEC 61850 name
LD0.FMMXU1
.Hz.mag
LD0.LLN0/LPHD1/LDEV1 System values
IEC 61850 name
LD0.LLN0
.ParChgCnt.stVal
LD0.MDSOPT1 Runtime counter for machines and devices (1)
Scale
IEC 61850 name
LD0.MDSOPT1
1
.OpTmh.stVal
LD0.MVI4GAPC1 Integer value move (1)
Scale
IEC 61850 name
LD0.MVI4GAPC1
1
.ISCS01.stVal
SA name
Description
0=Off; 1=Loc; 2=Rem; 3=Stat;
4=L+R; 5=L+S; 6=L+S+R; 7=S
+R
SA name
Description
F_DB
Frequency
SA name
Description
Num. of setting changes
SA name
Description
OPR_TIME
Total operation hours
SA name
Description
OUT1
- Integer value 1 (high)
- Low word
1MRS756878 H
Values
0...7
Values
35.00...75.00
[Hz]
Values
0...65535
Values
0...299999
Values
-/
+2147483647