1MRS756878 H
BitA
RegA
2838
177.06
2839
177.07
2840
177.08
2841
177.09
2.3.1.6
Table 9:

CTRL.DCSXSWI1 Disconnector position indication (1)

BitA
RegA
2792
174.08
2793
174.09
2794
174.10
2.3.1.7
Table 10:

CTRL.DCSXSWI2 Disconnector position indication (2)

BitA
RegA
2795
174.11
2796
174.12
2797
174.13
2.3.1.8
Table 11:

CTRL.DCSXSWI3 Disconnector position indication (3)

BitA
RegA
2798
174.14
2799
174.15
2800
175.00
2.3.1.9
Table 12:

CTRL.DCXSWI1 Disconnector control (1)

BitA
RegA
3472
217.00
3473
217.01
Table continues on next page
RET615
Point List Manual
IEC 61850 name
SA name
.BlkCls.stVal
BLK_CLOSE
.mcd
.ItlByPss.stVal
ITL_BYPASS
.mcd
CTRL.DCSXSWI1 Disconnector position indication (1)
IEC 61850 name
SA name
CTRL.DCSXSWI1
POSITION
.Pos.stVal.Close
-
.Pos.stVal.Open
-
.Pos.stVal.Fault
-
CTRL.DCSXSWI2 Disconnector position indication (2)
IEC 61850 name
SA name
CTRL.DCSXSWI2
POSITION
.Pos.stVal.Close
-
.Pos.stVal.Open
-
.Pos.stVal.Fault
-
CTRL.DCSXSWI3 Disconnector position indication (3)
IEC 61850 name
SA name
CTRL.DCSXSWI3
POSITION
.Pos.stVal.Close
-
.Pos.stVal.Open
-
.Pos.stVal.Fault
-
CTRL.DCXSWI1 Disconnector control (1)
IEC 61850 name
SA name
CTRL.DCXSWI1
POSITION
.Pos.stVal.Close
-
.Pos.stVal.Open
-
Modbus data mappings
Description
Close blocked
Interlock bypass
Description
Close bit
Open bit
Fault bit
Description
Close bit
Open bit
Fault bit
Description
Close bit
Open bit
Fault bit
Description
Close bit
Open bit
Section 2
Values
1=Blocked
1=Bypass
Values
1=Close
1=Open
1=Pos(00/11)
Values
1=Close
1=Open
1=Pos(00/11)
Values
1=Close
1=Open
1=Pos(00/11)
Values
1=Close
1=Open
19