Ctrl.dcxswi2 Disconnector Control (2) - ABB RET615 Manual

Transformer protection and control
Hide thumbs Also See for RET615:
Table of Contents

Advertisement

Section 2
Modbus data mappings
BitA
RegA
3474
217.02
3475
217.03
3476
217.04
3477
217.05
3478
217.06
3479
217.07
3480
217.08
3481
217.09
3482
217.10
3483
217.11
2.3.1.10
Table 13:

CTRL.DCXSWI2 Disconnector control (2)

BitA
RegA
3484
217.12
3485
217.13
3486
217.14
3487
217.15
3488
218.00
3489
218.01
3490
218.02
3491
218.03
3492
218.04
3493
218.05
3494
218.06
3495
218.07
20
IEC 61850 name
SA name
.Pos.stVal.Fault
-
.Pos.stSeld
-
CTRL.DCCILO1
.EnaOpn.stVal
ENA_OPEN
.EnaCls.stVal
ENA_CLOSE
CTRL.DCXSWI1
.BlkOpn.stVal
BLK_OPEN
.mcd
.BlkCls.stVal
BLK_CLOSE
.mcd
CTRL.DCCILO1
.ItlByps.stVal
ITL_BYPASS
.mcd
CTRL.DCXSWI2 Disconnector control (2)
IEC 61850 name
SA name
CTRL.DCXSWI2
POSITION
.Pos.stVal.Close
-
.Pos.stVal.Open
-
.Pos.stVal.Fault
-
.Pos.stSeld
-
CTRL.DCCILO2
.EnaOpn.stVal
ENA_OPEN
.EnaCls.stVal
ENA_CLOSE
CTRL.DCXSWI2
.BlkOpn.stVal
BLK_OPEN
.mcd
.BlkCls.stVal
BLK_CLOSE
.mcd
CTRL.DCCILO2
.ItlByps.stVal
ITL_BYPASS
.mcd
Description
Fault bit
Control selected
Open enabled
Close enabled
Open blocked
Close blocked
Interlock bypass
Description
Close bit
Open bit
Fault bit
Control selected
Open enabled
Close enabled
Open blocked
Close blocked
Interlock bypass
1MRS756878 H
Values
1=Pos(00/11)
1=Selected
1=Enabled
1=Enabled
1=Blocked
1=Blocked
1=Bypass
Values
1=Close
1=Open
1=Pos(00/11)
1=Selected
1=Enabled
1=Enabled
1=Blocked
1=Blocked
1=Bypass
RET615
Point List Manual