Honeywell GENT Nano panel-based Commissioning Instructions page 81

Fire detection and alarm system
Table of Contents

Advertisement

Commissioning instructions
Appendix D - old Mains powered interface unit
SECTOR
OFF
OFF
ZONE
OUTPUT
INPUT
End-of-line
Resistor
1
2
3
4
P3 to P6
S1 to S4
SWITCHES S1 to S4
MUST BE SET BEFORE
POWER UP
P3
P4
P5
P6
LED1
FS1
FS2
FS3
FS4
S5
S1
S2
S3
S4
1 2 3
1
P7
2
LK1
LK3
3
AC AC
2 - 12V 2.1Ah
SEALED LEAD ACID
BATTERIES
82
OUTPUT /
INPUT /
SECTOR
ZONE
End-of-line
Capacitor unit
BOARD
INTERFACE BOARD
FIXINGS
POINTS
P2
250mA
LED2
AUXILIARY
POWER
S6
FUSE
FS6
FS5
Aux
2.5A
Battery
BATTERY
P9
P8
FUSE
+ -
+
-
+
-
+
-
FOR INSTRUCTIONS ON THE NEW MAINS INTERFACE REFER TO
THE LEAFLET SUPPLIED WITH THE PRODUCT.
Ratings
Zone
24V nominal 2mA
(input)
maximum
24V nominal 500mA
Sector
(output)
maximum (500mA
total for all sectors)
Auxiliary
24V nominal 250mA
maximum
power
output
When lit it indicates
LED1
(green)
local mains power is
healthy
LED2
When lit it indicates
communication with
(yellow)
loop circuit has
failed
Fail safe mode
¨
In this mode if there is a loop communication failure lasting over 1 minute duration, then all
the outputs of the unit are activated (switched On). The outputs deactivate on restoration of loop
communication. On pressing the reset button on the PCB you can restore outputs to their
normal state.
¨
If there are three communication failures over 10 minutes duration the outputs will be latched
On, in this case the unit must be powered down and powered up again to unlatch and restore the
unit for normal operation.
Link
Position
Meaning
LK1
1 - 2 #
Normal zone voltage
LK1
2 - 3
Low zone voltage
'Reduces the zone voltage
by 4V for Thorn detectors'
LK3
1 - 2#
Fail safe disable
LK3
2 - 3
Fail safe enable
# - factory settings
S5 - rotary
0 -GENT detectors
switch
S6
Reset push button (fail
safe)
4188-949 issue 3_05/10_Nano Comms inst.