Commissioning
The factory default settings shown in the table below will be appropriate for most applications. However, the installer does have the
facility to re-programme all parameters using the HP2000 Programmer. These parameters may be re-programmed any number of
times and all settings will be retained in the event of a power loss.
Parameter
Options
Power Up
On / Off
Response
Auto, Manual/Bus, Manual only
Off Delay
1 min - 96 hrs, 10-sec (walk-test), Disabled 20 mins
On Sensitivity
0-100
Bus Connect
Yes / No
1st - 4th Zone
Address 1-100; -- (no zone); Common 1-3
Corridor 1 & 2
0-100; -- (no zone); Building
Global 1 & 2 Rx
Yes / No
Manual Input
Shared / Local
Start Lamps
Max / Min
Entry Scene
1-6
Bright Out
Yes / No
Dimming
Reg 50%-Reg100%
Lamp Max
10%-100%
Fade to Off
Yes / No
When Vacant
Off / Min / Reg <25% / Scene 6
Set-point Low
0-1023
Set-point High
0-1023
Additional feature accessible under Utilities on HP2000:
100 Hour Burn-In Burn-in 100 hrs / Cancel / Resume
Lens Mask
A lens mask (HBPIRLM) is available to mask end-of-aisle movement from being detected.
Important Additional Notes
1.
All terminals on this product are provided for final connections. It is not intended that the product be used as a junction box
for looping cables.
2.
A means for disconnection must be incorporated in the fixed wiring in accordance with the current wiring regulations.
3.
Although nominally 12V, the dimming output is not SELV and therefore should be treated with the same respect as mains
with regard to wiring practice. The 0V line of the dimming output is almost at Neutral potential.
4.
The dimming control output should be connected only to the control input of the ballasts - never to other detectors.
5.
Due to the fact that the photocell is on the ceiling looking down, it is not possible for measurements made with a lux meter on
the working plane to remain constant when daylight illuminates the ceiling and the working plane to a differing extent.
Therefore, products of this type should be regarded as capable of maintaining an APPROXIMATE light level only.
Pre-Set
Notes
Sets the luminaire state at power up irrespective of occupancy.
On
Useful in reducing start-up load following power cut. Power-up off -
responds to occupancy after 30 seconds.
Auto
If set to Auto, the presence detector switches the luminaire on and
off automatically. If set to Manual Only, it can only be turned on by
using OneSwitch or the hand-held controller. If set to Manual/Bus,
an MLS Bus turn-on command for a Zone to which the detector
belongs will also bring the light on. In all modes the "When Vacant"
behaviour (below) is initiated automatically.
The time for which the luminaire will stay on following the last
detected movement. Also 10-second setting for walk-testing.
100
Sensitivity to movement when area is occupied. 100 = max
Yes
Do/Do not Signal/Receive on MLS Bus.
No Zone
Individual Zones influencing and being influenced by this detector.
No Zone
Zone ranges influencing and being influenced by this detector.
No
Respond to selective load shedding.
Local
Do/Do not signal OneSwitch commands across the MLS Bus.
Max
Sets the level at which the lamps strike when turning on.
Scene 1
Sets which scene is recalled when unoccupied area is entered.
No
If set to yes, movement fails to refresh the off delay if ambient light
level exceeds 125% of set level and the luminaire will switch off
when the off delay has elapsed. NB: Dimming must be set to 100%.
100%
Can be set to operate between 50% and 100% ballast output from
max down to a bottom-end limit when working on photocell control.
Can be set to limit the absolute maximum output of the ballast in all
100%
operating modes.
No
When no presence is detected, and after the off delay period, the
lamps can fade out instead of switching off (approx 80 seconds to
fade from 100% to 0%).
Off
Options for a vacant area after it has timed out. Luminaires can turn
off, remain at minimum output, or regulate with a 25% output limit,
until the next period of occupancy. If programmed to remain at
minimum, to regulate below 25% or go to scene 6, there are further
programmable options to switch off after 3 times the Off Delay (XTN)
or when no further movement has been detected anywhere in the
building (BLD).
1023
Aiming point as photocell adjusts ballast output.
1023
Level above which photocell switches its output off (only if Bright
Out = Yes).
0 hr
See Application Note: AN4028