8.1.13 How Do I Configure ECC800 Alarm Parameters?

Context
Procedure
Step 1 Log in to the ECC800 WebUI as an administrator.
Step 2 Choose System Settings > Alarm Parameters.
Step 3 On the Basic Alarm Parameters page, choose ECC800 from the Select a device type
drop-down list box, choose the ECC800 to be set from the Device name drop-down list box,
and then click Confirm.
Step 4 Set Enable Alarm to Enable or Disable for Operation log full as required. Set Severity to
Critical, Major, Minor, or Warning as required.
Step 5 On the Alarm Linkage page, set Device type to ECC800, select Device Type or Device in
the Linkage type column, and click Confirm.
Step 6 (Optional) If you select Device in the Linkage type column, select the ECC800 to be set in
the Device name column.
Step 7 Click Select in the Output Dry Contact column corresponding to Operation log full as
required, select Yes or No for DO1 or DO2, and click OK.
Select a DO not used by other functions. Otherwise, the association setting fails.
Step 8 Click Select in the Loudspeaker column corresponding to Operation log full as required, set
Loudspeaker to Yes or No, and click OK.
----End
Issue 05 (2019-09-16)
You can set parameters under Enable Alarm, Severity, Output Dry Contact and
Loudspeaker based on requirements.
When Enable Alarm is set to Disable for an alarm, the ECC800 will not show this
alarm.
You can set Severity to Critical, Major, Minor, or Warning as required.
After an alarm and a DO output are associated over Output Dry Contact, the
device connected to the DO port will act if the alarm is generated.
If an alarm is associated with the loudspeaker and Loudspeaker is set to Enable,
the loudspeaker produces sound when the alarm is generated.
You can modify alarm parameters in batches over Batch Setting.
The setting methods for different alarms are the same. This section describes how to set
the Operation log full alarm for the ECC800.
To modify Enable Alarm or Severity in batches, click Batch Setting in the left corner of the Basic Alm
Para page, and choose ECC800 from the Select a device type drop-down list box. Set Destination
Parameter of Enable Alarm or Source Parameter and Destination Parameter of Severity, and click
OK.