ABB Relion 670 Series Applications Manual page 450

Bay control, version 2.1 ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 16
Monitoring
It is also possible to initiate the counter from a non-zero value by resetting the function to the
wanted initial value provided as a setting.
If applicable, the counter can be set to stop or rollover to zero and continue counting after
reaching the maximum count value. The steady overflow output flag indicates the next count after
reaching the maximum count value. It is also possible to set the counter to rollover and indicate
the overflow as a pulse, which lasts up to the first count after rolling over to zero. In this case,
periodic pulses will be generated at multiple overflow of the function.
16.9.3
Setting guidelines
The parameters for Limit counter L4UFCNT are set via the local HMI or PCM600.
16.10
Running hour-meter TEILGAPC
16.10.1
Identification
Function Description
Running hour-meter
16.10.2
Application
The function is used for user-defined logics and it can also be used for different purposes
internally in the IED. An application example is to accumulate the total running/energized time of
the generator, transformer, reactor, capacitor bank or even line.
Settable time limits for warning and alarm are provided. The time limit for overflow indication is
fixed to 99999.9 hours. At overflow the accumulated time resets and the accumulation starts from
zero again.
16.10.3
Setting guidelines
The settings
resolution of the settings is 0.1 hours (6 minutes).
The limit for the overflow supervision is fixed at 99999.9 hours.
The setting
444
IEC 61850
identification
TEILGAPC
tAlarm and tWarning are user settable limits defined in hours. The achievable
tAlarm and tWarning are independent settings, that is, there is no check if tAlarm >
tWarning .
tAddToTime is a user settable time parameter in hours.
IEC 60617
ANSI/IEEE C37.2 device
identification
number
-
-
1MRK 511 358-UUS A
GUID-5AECCDBC-7385-4D9F-940C-9D4A0E59B106 v1
GUID-DA5DA8D7-4821-4BFB-86CC-28658E376270 v1
GUID-3F9EF4FA-74FA-4D1D-88A0-E948B722B64F v1
GUID-225D8341-2D31-49F1-9B49-571346C0FE26 v1
GUID-D3BED56A-BA80-486F-B2A8-E47F7AC63468 v1
Application manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rec670

Table of Contents