VDLDPU with a sufficient margin below the minimum expected operating voltage. A safety
Set the
margin of at least 15% is recommended.
12.3

Fuse failure supervision VDSPVC (60)

12.3.1

Identification

Function description
Fuse failure supervision
12.3.2

Application

Some protection functions operate on the basis of measured voltage at the relay point. Examples
of such protection functions are distance protection function, undervoltage function and
energisation-check function. These functions might mal-operate if there is an incorrect measured
voltage due to fuse failure or other kind of faults in voltage measurement circuit.
VDSPVC is designed to detect fuse failures or faults in voltage measurement circuit based on
comparison of the voltages of the main and pilot fused circuits phase wise. VDSPVC output can be
configured to block voltage dependent protection functions such as high-speed distance
protection, undervoltage relays, underimpedance relays and so on.
250
IEC 61850
IEC 60617
identification
identification
VDSPVC
VTS
1MRK 511 358-UUS A
GUID-9C5BA1A7-DF2F-49D4-A13A-C6B483DDFCDC v2
GUID-109434B0-23E5-4053-9E6E-418530A07F9C v2
ANSI/IEEE C37.2
device number
60
GUID-AD63BF6C-0351-4E48-9FB2-9AB5CF0C521E v2
Application manual