Section 16
Monitoring
For Disturbance report function there are a number of settings which also influences the sub-
functions.
Three LED indications placed above the LCD screen makes it possible to get quick status
information about the IED.
Green LED:
Steady light
Flashing light
Dark
Yellow LED:
Steady light
Flashing light
Red LED:
Steady light
Flashing
Operation
The operation of Disturbance report function DRPRDRE has to be set
Disabled is selected, note that no disturbance report is registered, and none sub-function will
operate (the only general parameter that influences Sequential of events (SOE)).
Operation = Disabled :
Disturbance reports are not stored.
LED information (yellow - pickup, red - trip) is not stored or changed.
Operation = Enabled :
Disturbance reports are stored, disturbance data can be read from the local HMI and from a
PC using PCM600.
LED information (yellow - pickup, red - trip) is stored.
Every recording will get a number (0 to 999) which is used as identifier (local HMI, disturbance
handling tool and IEC 61850). An alternative recording identification is date, time and sequence
number. The sequence number is automatically increased by one for each new recording and is
reset to zero at midnight. The maximum number of recordings stored in the IED is 100. The oldest
recording will be overwritten when a new recording arrives (FIFO).
436
In Service
Internal failure
No power supply
A Disturbance Report is triggered
The IED is in test mode
Triggered on binary signal N with
The IED is in configuration mode
To be able to delete disturbance records,
SetLEDN = Enabled
Enabled or Disabled . If
Operation parameter has to be Enabled .
1MRK 511 358-UUS A
M12179-82 v5
Application manual