Ambient conditions
Ambient conditions
(cont.)
EMC (at default
settings)
Noise level
Safety
Ambient operating
temperature
Storage temperature
Relative humidity
Air quality:
• chemical vapours
• mechanical particles
Altitude
Vibration
EN61800-5-1/
EN60068-2-6
Shock
EN61800-5-1
EN60068-2-27
Enclosure class
Immunity
Emissions
Average noise level
(cooling fan) sound
power level in dB(A)
I
: -10°C (no frost)...+40°C; up to +50°C
L
with derating
-40°C...+70°C
0...95% RH, non-condensing, non-corrosive
Tested according to IEC 60068-2-60 Test
Ke: Flowing mixed gas corrosion test,
Method 1 (H
S [hydrogen sulfide] and SO
2
[sulfur dioxide])
Designed according to:
IEC 60721-3-3, unit in operation, class 3C2
IEC 60721-3-3, unit in operation, class 3S2
100% load capacity (no derating) up to
1,000 m
1-% derating for each 100m above 1,000m
Max. altitudes:
208...240V: 4,500m (TN and IT systems)
380...480V: 4,500m (TN and IT systems)
Voltage for I/O signals:
Up to 2,000m : Allowed up to 240V
2,000m...4,500m: Allowed up to 120V
Corner-grounding: up to 2,000m only.
5...150 Hz
Displacement amplitude 1 mm (peak) at
5...15.8 Hz (MR4...MR9)
Max acceleration amplitude 1 G at
15.8...150 Hz (MR4...MR9)
UPS Drop Test (for applicable UPS weights)
Storage and shipping: max 15 G, 11 ms (in
package)
IP21/NEMA1 (HVACxxx-xxx-21)
IP54/NEMA12 (HVACxxx-xxx-54)
Note! Keypad required for IP54/Type 12
Fulfils EN61800-3 (2004), first and second
environment
EN61800-3 (2004), Category C2
The drive can be modified for IT-networks.
See chapter 6.3.
MR4: 65
MR7: 77
MR5: 70
MR8: 86
MR6: 77
MR9: 87
EN 61800-5-1 (2007), CE, cUL; (see unit
nameplate for more detailed approvals)
T
ECHNICAL DATA