Connect the stripped cables (see Figure 14 and Figure 18) as shown in
Figure 21.
•
Expose the shield of all three cables in order to make a 360-degree con-
nection with the cable clamp (1).
7
•
Connect the (phase) conductors of the supply, brake and motor cables
into their respective terminals (2).
•
Form the rest of the cable shield of all three cables into "pigtails" and make
a grounding connection with a clamp as shown in Figure 21 (3). Make the
pigtails just long enough to reach and be fixed to the terminal - not longer.
Figure 20.
L1L2L3
3
2
1
Figure 21.
R+ R- U V W
P
OWER CABLING
3