Connecting Eaglehawk Nx Via Its Rs485-2 Interface To A Modbus - Honeywell CENTRA LINE EAGLEHAWK NX Installation & Commissioning Instructions

Table of Contents

Advertisement

EAGLEHAWK NX CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

Connecting EAGLEHAWK NX via its RS485-2 Interface to a Modbus

With regards to Fig. 50, please note the following:
NOTE: Always power each EAGLEHAWK NX controller and the connected Modbus slaves via separate transformers.
NOTE: For "L," see section "RS485 Standard" on pg. 10.
NOTE: If any of the devices are electrically isolated, it is recommended that those devices be connected to signal ground. See
section "RS485 Standard" on pg. 10.
NOTE: Between devices equipped with non-isolated RS485 bus interfaces, potential differences of max. ±7 V are allowed.
Further, this bus should not extend beyond a single building.
Example: EAGLEHAWK NX Modbus Master Controller and Connected Modbus Slaves (with inserted
termination resistor)
EAGLE-
HAWK NX
2930 31
GND-2
+5V
GND-2
Module #2
550 OHM
130 OHM
550 OHM
RS485-2 (+) RS485-2 (-)
NO EFFECT ON RS485-2
1 2
Modbus
Module #1
F1
24 V
230 V
Fig. 50. Connection of an EAGLEHAWK NX Modbus master controller via its RS485-2 interface to a Modbus with slaves
The termination resistor must be inserted directly into the terminals of the last Modbus slave.
NOTE: In this example, a maximum of one of the Modbus RTU slaves can be an EAGLEHAWK NX Modbus RTU slave –
which must then be positioned at the end of the Modbus (as "Modbus Module #N"); the insertion of the aforementioned
termination resistor is then unnecessary.
Modbus
Modbus
Module #3
*CONNECT GND, IF AVAILABLE.
L
Modbus
Module #4
45
Modbus
Modbus
Module #N-1
Module #N
EN1Z-1039GE51 R1218
R
T
120 OHM

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents