EAGLEHAWK NX CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
CLNXxxx26xxx Connection Examples
TOTALIZER
1: GND
2: SIGNAL
1
2
24 25 26
~
1
2
24Vac
!
WARNING
Risk of electric shock or equipment damage!
Low voltage and line voltage must not be wired
within the same block.
For fusing specifications see section "Fusing Specifications" on page 20.
NOTE: Use a min. distance of 10 cm between power cables and 0...10 V / sensor cables in order to prevent signal
disturbances on the 0...10 V / sensor cables.
EN1Z-1039GE51 R1218
DRY
NTC20kOHM
CONTACT
SENSOR
1: GND
1: GND
2: SIGNAL
2: SIGNAL
1
2
27 28 29 30 31 32
33 34 35 36
CLNXEH26ND100A
BLOCK 1
5
6
7
8
9 10
FAN
1
1: GND
FAN
2: 24V~
1: 24V 0
~
2: 24V
M
~
Fig. 27. CLNXxxx26xxx connection example
NTC20kOHM
SENSOR
1: GND
2: SIGNAL
1
2
1
37
38 39
40 41 42 43 44 45 46 47
BLOCK 2
11 12 13 14 15 16 17 18
L
N
FAN
2
1
2
1: 230V N
FAN
2:
230V~
1: 24V 0
~
2: 24V
M
~
24
ACTIVE SENSOR
1: GND (24V 0)
~
2: 24V POWER
~
3: 0...10 VDC
2
1
2
3
1
2
19
20
21
22
23
1
2
24V
~ DRIVE with
1
2
3
0...10V SIGNAL
1: GND (24V 0)
~
2: 24V POWER
~
M
0...10 VDC
3: 0...10 VDC