Final Wiring Check

1. Check the power supply circuit. The voltage and
frequency tolerance must match those of the RM7838A.
A separate power supply circuit can be required for the
RM7838A. Add the required disconnect means and
overload protection.
Table 3. Terminal Ratings.
Description
a
Flame Sensor Ground
1
Earth Ground
Line Voltage Common
Alarm
Line Voltage Supply (L1)
Unused
Start/Stop Switch Input
Running Interlock
Intermittent Pilot
Main Fuel Valve
Ignition
Flame Sensor
Unused.
High Fire Switch Input
Unused
Run Enable/Flame Proven
Shutter
Table 4. Combinations for Terminals 8, 9 and 10.
Pilot Fuel 8
C
B
F
F
D
D
D
Table 5. Composition of each Combination.
B
RM7838A 7800 SERIES RELAY MODULES
120 Vac, 1A pilot duty.
120 Vac, (+10/-15%), 50/60- Hz (±10%)
120 Vac, 1 mA.
120 Vac, 8A run, 43A inrush.
c
120 Vac.
c
120 Vac.
c
120 Vac.
60 to 220 Vac, current limited.
120 Vac, 1 mA.
120 Vac, 2A pilot duty.
120 Vac, 0.5A.
Main 9
F
F
F
No Load
F
D
No Load
C
180 VA Ignition plus
2A Pilot Duty
Motor valves with:
660 VA inrush,
360 VA open,
250 VA hold.
2. Check all wiring circuits and complete Static Checkout
in Table 7 before installing the RM7838A on the
subbase.
3. Install all electrical connectors.
4. Restore panel power.
5
Ratings
b
Ignition 10
No Load
No Load
A
A
A
A
A
D
F
65 VA Pilot Duty plus
Motor valves with:
3850 VA inrush,
700 VA open,
250 VA hold.