EP03-300-200
Release 200

ControlNet Specifications

Table 4. 9904-KTCX15, TC-PCIC01, TC-CCN013, TC-CCR013, TK-CCR013
Parameter
Data rate
Redundancy
ControlNet Components
Cable Type and Topology
Cable Type by Application
Light industrial applications
Heavy industrial applications
High and low temperature applications,
as well as corrosive (harsh) areas
Moisture Resistant (direct burial,
flooding, etc.)
Maximum Distance and Total
number of Repeaters Between any
two (2) Nodes
Maximum Coax Segment Length
Maximum Fiber Segment Length
Maximum Total Length Differential
Between A and B Trunk
Fiber Optic Repeater Specifications – TC-RPA002, TC-RPRS01, TC-RPFM01
Mounting
Maximum number of Fiber Modules per
TC-RPA002 ControlNet Module Adapter
Power Requirements (TC-RPA002)
Fiber Optic Repeater Model
Optical power budget
Cable wavelength specification
Fiber Type
Fiber Termination Type
Maximum fiber optic segment distance is dependentupon the quality of the fiber, number of splices, and connectors. For more
ControlNet topology information, refer to the Planning Guide in Knowledge Builder or to EP-DCXX21.
Loc al ControlNet Trunk
Tap
24 Vdc
Figure 3. ControlNet Fiber Optic Example -- Use of 2 Fiber Segments to
Interconnect 2 Non-Redundant-Media ControlNet Trunk Segments
Experion PKS CEE-based Controller Specifications and Models
5 Mbit/sec
Single cable or redundant operation supported
End devices (workstations and controllers), taps, trunk cable, cable
connectors, terminators, segments, repeaters, and bridges.
RG-6 Quad Shield cable, BNC connectors, trunk & drop, bus
topology. See next page for recommended cable types.
Standard PVC CM-CL2
Lay-on Armored and Interlocking Armor
Plenum FEP CMP-CL2P
Flood burial
Maximum Coax plus Fiber length of 10 km
Maximum of 5 Repeaters (6 Segments)
1000 m (3280 ft.) - 16.3 m (53.4 ft.) x [number of Taps - 2]
See Repeater Specifications below
800 m (2624 ft.) (total link)
DIN rail mountable (35 mm wide rail)
Four (2 ports/module)
24 VDC, 700 mA maximum
TC-RPFS01 (300 M)
200 µm glass (HCM)
Remote ControlNet Trunk
Tap
TC- RPA001
TC- RPFM01
R1 T1
R2 T2
R1
T1
R 2
T2
TC- RPA001 TC- RPFM01
24 Vdc
Fiber Segments -- 3 Km m ax each
Specification
4.2 dB
650 ηm (red)
Versalink
TC- RPA001
TC- RPFM01
24 Vdc
R1 T1
R2 T2
R1
T1
R2
R1 T1
R2 T2
R 1
T1
R 2
T2
17
December, 2003
Version 1.0
TC-RPFM01 (3000 M)
9.3 dB
1300 ηm
62.5 µm
ST Termination
TC- RPFM01
R1 T1
R2 T2
T2
R 1
T1
R2
T2