EP03-300-200
Release 200
Compliance to European Union Directives. This product has the CE mark and is approved for
installation within the European Union and EEA regions. It has been designed and tested to meet the
following directives:
EMC Directive. This apparatus is tested to meet Council Directive 89/ 336/ EEC Electromagnetic
Compatibility (EMC) using a technical construction file and the following standards, in whole or in
part:
EN 50081- 2 EMC – Generic Emission Standard, Part 2 – Industrial Environment
EN 50082- 2 EMC – Generic Immunity Standard, Part 2 – Industrial Environment
The product described in this document is intended for use in an industrial environment.
Low Voltage Directive. This product is also designed to meet Council Directive 73/ 23/ EEC Low
Voltage, by applying the safety requirements of EN 61131– 2 Programmable Controllers, Part 2 –
Equipment Requirements and Tests.
Table 2. Agency Standards Compliance
Agency
Standard
CE Mark
Standard Compliance
CSA
C22.2 No. 142-M1983
C22.2 No. 0-M1982
C22.2 No. 4-M1982
FM
ISA S12.12
UL
C-Tick
Australian
Radiocommunications
Act of 1992

Control Processor Module Hardware Specifications

The Experion PKS C200 Control processor module meets the following specifications:
Table 3. TC-PRS021, TK-PRS021 Specifications
Parameter
Module Power Requirements
Module Battery Backup Time
Lithium Battery (standard, built in)
Battery Extension Module (BEM)
1
CPM backup is provided via the Lithium Battery or the Battery Extension Module (BEM), but not by both. The Lithium
battery must be removed from the Control Processor if a BEM is used in the rack. A label inside the CP front door
provides that warning.
2
The 1/2AA Lithium Battery has a non-restricted classification due to its size. It can be shipped without any special
documentation or note on the shipping list. The battery is specified for operation from -55 °C to +85 °C.
See Table 1 (previous page) for all general environmental specifications and agency certifications.
Experion PKS CEE-based Controller Specifications and Models
Electrical Emissions and Susceptibility
Process Control Equipment
General Requirements Canadian Electrical Code, Part II
Bonding and Grounding of Electrical Equipment
Non-incendive Electrical Equipment for Use in Class I & II, Div.
2 and Class III, Div 1 & 2 Hazardous (Classified) Locations
508
Industrial Control Equipment
Electromagnetic Compatibility
Operative and Storage Limits
+5 VDC +/- 5% @ 1.5 A
+3.3 VDC +/- 5% @ 1.0 A
1
144 hours (non-rechargeable,
replaceable) - 6 days
120 hours (rechargeable) - 5 days
Description
16
December, 2003
Version 1.0
Transportation Band
Lithium battery is
disconnected during
2
shipment.