L8124A,B,C,E,G,L,M AQUASTAT® RELAYS
IMPORTANT
1. Terminals on these Aquastat relays are approved
only for copper wire.
2. Immersion well must snugly fit sensing element and
bulb must rest against bottom of well. Bend the
tubing, if necessary, to hold bulb against the bottom
of the well. Do not make a sharp bend in the tubing
that can produce a break in the tubing and cause
loss of fill. This condition will cause the high and low
limit controllers to be made continuously.
Mounting Standard Models
The boiler must be provided with a tapping that allows
horizontal mounting of the well. It should be located where
boiler water of average temperature can circulate around the
well.
To mount the L8124, proceed as follows:
1. Turn off all power and drain the boiler.
2. If no tapping is provided, prepare one that is properly
sized and threaded at the location selected.
3. Install the immersion well (ordered separately) in the
boiler tapping and tighten securely.
NOTE: Do not attempt to tighten the well using the case as a
handle.
4. Refill the boiler and check for water leakage.
5. Loosen, but do not remove, the clamp screw on the
bottom (L8124A,B,E,G) or on the top (L8124C,L,M)
of the case.
6. Insert the element in the well until it bottoms.
7. Fit the case onto the well so that the clamp on the case
slides over the flange on the well. Securely tighten the
clamp screw.
TRADELINE Models
IMPORTANT
Use the heat-conductive compound furnished with
the TRADELINE L8124 to obtain best thermal
response. Fold the plastic bag of compound
lengthwise and twist it gently. Snip off end and work
open end of the bag all the way into the well. Slowly
pull out the bag while firmly squeezing it to evenly
distribute the compound.
Position the mounting bracket on the back of the case for
mounting the case horizontally or vertically as desired. See
Fig. 8.
1. Shut off the electric power and remove the old control.
Leave the old immersion well in place if it is suitable for
use with the L8124, either with or without an adapter. A
124904 Well Adapter can be ordered separately; see
form 68-0040, Immersion Wells and Compression
Fittings, for ordering information.
2. If the old well is unsuitable, drain the system, remove
the old well, and install a new immersion well. Refill the
system. Refer to form 68-0040, Wells and Fittings for
Temperature Controllers, to order a new well. Make
sure the well is tightly screwed in to prevent leakage.
60-2061—10
NOTE: Do not attempt to tighten the well using the case as a
handle.
3. Loosen, but do not remove, the immersion well clamp
screw.
4. If the immersion well fits the L8124 Immersion Well
Clamp, proceed as follows:
a. Partially fill the immersion well with heat-conductive
compound.
b. Insert the bulb into the well. The bulb must bottom in
the well.
c. Make sure the well fits into the hole in the case.
Properly position the clamp on the well flange; then
tighten the clamp screw.
d. Center the loop of excess capillary tubing in front of
the immersion well so it cannot touch any electrical
parts.
NOTE: Some models have a tubing length adjustable to
3 in. (76 mm). In these models, pull out extra tubing
from inside the case if needed.
5. If the old immersion well is otherwise suitable but does
not fit the L8124 Clamp, a 124904 Well Adapter,
ordered separately, must be used as follows:
a. After loosening the immersion well clamp screw, fit
the adapter onto the capillary tube (Fig. 9).
b. Make sure the adapter fits into the hole in the case.
Properly position the clamp on the adapter flange;
then tighten the clamp screw.
c. Return to step 4a above, and complete the
installation.
BRACKET POSITION FOR
VERTICAL MOUNTING
Fig. 8. Convertible case on tradeline models is
designed for horizontal or vertical mounting.
6
BRACKET POSITION FOR
M1798
HORIZONTAL MOUNTING