Function

3 .11 Statistics

The statistical data stored in the unit, such as fault sig-
nals which have occurred, various counter readings and
measured values, is displayed in statistics in BCSoft.
The counters and measured values ranges are each
split into overall data and customer data. The customer
data is used for recording information over a specific
period.

3 .11 .1 Counters

Actuating cycles (0 – 100 – 0%), changes of direction
(Open/Close), switching of the output relays, "Power
On" switching operations and mains operating hours
are added in the statistics. Besides the total counters,
there are customer counters for recording information
over a specific period.

3 .11 .2 Measured values

The minimum and maximum internal housing tempera-
tures are saved in statistics. In addition, the current in-
ternal temperature is displayed. Here as well, there is a
customer memory for viewing a period.
IC 40 · Edition 07.18

3 .11 .3 Resetting statistics

All signals and customer data can be reset. The reset
date is saved automatically and displayed together with
the customer data.
Total counter and measured values cannot be reset or
deleted.

3 .11 .4 Resetting a signal

A fault signal is signalled by the red LED on the actuator.
The detailed cause of the signal is displayed in BCSoft.
The cause must be remedied. The signal can then be
acknowledged and reset with BCSoft.