Table 10- 44 PM240-2, IP20, FSE, 3 AC 500 V ... 690 V
Article No. - without filter
Article No. - with filter
LO base load power
LO base load input current
LO base load output current
HO base load power
HO base load input current
HO base load output current
Siemens fuse according to IEC/UL
Fuse according to IEC/UL, Class J
Power loss without filter
Power loss with filter
Required cooling air flow
Weight without filter
Weight with filter
Current derating depending on the pulse frequency
Article number
6SL3210-1PH21-4❒L0
6SL3210-1PH22-0❒L0
6SL3210-1PH22-3❒L0
6SL3210-1PH22-7❒L0
6SL3210-1PH23-5❒L0
6SL3210-1PH24-2❒L0
6SL3210-1PH25-2❒L0
6SL3210-1PH26-2❒L0
The permissible motor cable length also depends on the cable type and the selected pulse fre-
1)
quency.
Converter with CU230P-2 Control Units
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB
6SL3210-...
...1PH25-2UL0
6SL3210-...
...1PH25-2AL0
45 kW
50 A
52 A
37 kW
44 A
42 A
3NA1 820 / 80A
80 A
1.00 kW
1.00 kW
83 l/s
26 kg
28 kg
LO base load output current for a pulse frequency of ...
10.2 Technical data, Power Modules
...1PH26-2UL0
...1PH26 -2AL0
55 kW
59 A
62A
45 kW
54 A
52 A
3NE1 820 / 80A
80 A
1.21 kW
1.22 kW
83 l/s
26 kg
28 kg
for 690 V devices
1)
[A]
2 kHz
14
19
23
27
35
42
52
62
Technical data
4 kHz
8.4
11.4
13.8
16.2
21
25.2
31.2
37.2
405