Download Print this page
Honeywell V5197A1011 Product Data

Honeywell V5197A1011 Product Data

Firing rate gas valve

Advertisement

Quick Links

APPLICATION
The V5197A is a firing rate valve used to provide variable
flow control of air, natural gas, liquefied petroleum (LP), and
manufactured gases. The V5197A is actuated by a firing rate
motor that can be mounted directly on the valve. The V5197A
is not applicable as a safety shutoff valve.
The V5197A is specially designed to provide fine control
of gas flow in applications where a high turn down ratio is
required.
The maximum flow adjustment screw on the bottom of the
valve allows adjusting the maximum flow of gas through the
V5197 while maintaining the linear modulating characteristics
and stroke.
The V5197A is part of the Honeywell Integrated Valve Train
System that allows gas train components to be directly bolted
together.
® U.S. Registered Trademark
Copyright © 2003 Honeywell International Inc.
All Rights Reserved
Firing Rate Gas Valve
FEATURES
• Used with air, natural, manufactured or liquefied
petroleum (LP) gases.
• For modulating applications that do not require final
shutoff service of firing rate valve.
• Two valve body types (small and large) applicable to
seven pipe sizes:
• Small body type for 3/4 in. (19 mm), 1 in. (25 mm),
1-1/4 in. (32 mm), 1-1/2 in. (38 mm) and 2 in. (51 mm)
pipes, NPT or ISO 7 threads.
• Large body type for 2 in. (51 mm), 2-1/2 in. (64 mm)
and 3 in. (76 mm) pipes, NPT or ISO 7 threads.
• Two downstream 1/4 in. NPT threaded pressure taps
available.
• Accepts C6097 Pressure Switch mounted directly to
flange (downstream pressure tap only).
• Unpainted cast aluminum body.
• Suitable for electric or pneumatic operators with the
appropriate linkage.
• May be used with manufacturers own linkage and
drive motor.
• Flow adjustment screw on bottom of valve controls
maximum flow.
• Visual position indicator.
Application ........................................................................
Features ...........................................................................
Specifications ...................................................................
Ordering Information ........................................................
Installation ........................................................................
Checkout and Operation ..................................................
Service Information ..........................................................
V5197A
PRODUCT DATA
Contents
1
1
2
2
5
8
8
65-0247-2

Advertisement

loading

Summary of Contents for Honeywell V5197A1011

  • Page 1 Contents V5197 while maintaining the linear modulating characteristics and stroke. Application ................ Features ................The V5197A is part of the Honeywell Integrated Valve Train Specifications ..............System that allows gas train components to be directly bolted Ordering Information ............together.
  • Page 2: Specifications

    If you have additional questions, need further information, or would like to comment on our products or services, please write or phone: 1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory). 2. Honeywell Customer Care...
  • Page 3 M17524B Fig. 4. V5197A (small body) flow curves at stated Fig. 1. V5197A (small body) flow curves at stated pressure drops with flow adjustment set at 25%. pressure drops with flow adjustment set at 100%. V5197A1011 V5197A1003 14000 16000 12000...
  • Page 4 V5197A FIRING RATE GAS VALVE 32000109-005 2 in. (51 mm—small body valve only. 32001605-001 2 in. (51 mm)—large body valve only. V5197A1011 32001605-002 2-1/2 in. (64 mm). 32001605-003 3 in. (76 mm). 16000 Pipe Adapters, BSP: 14000 32000109-006 3/4 in. (19 mm).
  • Page 5 V5197A FIRING RATE GAS VALVE 7-1/8 7-15/16 (181) (202) 10-5/16 12-11/16 (277) (322) 3-25/32 4-3/4 (96) (121) 6-7/16 (165) 9-1/4 (235) 4-27/32 (123) 2-1/2 (64) 4-13/16 (122) 4 (102) M17528 M17898 Fig. 10. V5197A Firing Rate Gas Valve (small body), with mounting bracket (included) and ML7999 Actuator (not supplied), dimensions in in.
  • Page 6 Refer to the Integrated Valve Train Installation instructions shown in Fig. 13. (form 66-1099) for complete instructions on mounting a V5197A in a Honeywell Integrated Valve Train System. NOTE: Tightening torque for nuts/bolts: Allow sufficient clearance for assembling the motor and •...
  • Page 7 V5197A FIRING RATE GAS VALVE CORRECT: NORMAL INCORRECT: TOO LONG, FULL THREAD DISTORTS VALVE SEAT LOOSE CHIPS V5197 TWO CLEAN THREADS EXCESS DOPE WITH MODERATE CAN BLOCK DISK AMOUNT OF DOPE FROM VALVE SEAT REAM PIPE AND BLOW PIPE OUT CHIPS (TO AVOID ADAPTER PIPE LODGING ON SEAT)
  • Page 8: Service Information

    Automation and Control Solutions Honeywell International Inc. Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive...

This manual is also suitable for:

V5197a1003V5197a series