Zone indicators

The zone indicators are not used on a BS Repeat panel. The
links that disable the zone indicators are located on the bottom
edge of the DKC and must be set to 'Without zone indicators'
position. The links are factory set for EN Repeat panel that is
'With zone indicator', see illustration on the right.

Display selection

"
The rotary switch SW3 is located on the Master
Repeat Card and must be set in the correct position for
the type of display used, factory set to position 4.
SW3
position Panel
0
A2/A3/A4 Mimic Panel only
1
3400 Repeat panel
(having a 4 line display)
2
32000 Repeat panel
(having a 16 line display)
3
Vigilon Repeat panel
(having a 16 line display)
4
Vigilon Repeat panel
(having an 8 line display)
5 to F
Not used
SW3
SW1
RESET
WRITE PROTECT
P4
P2
SW3
P1
BUZZER
DISABLE
WD1
P7
FS3
P14
USB
2A(QB)
PB2
-
+
0V 24V
RS485
P14
P14
Write Protected
(Factory setting)
Buzzer
Buzzer Not
Disable
Disable

Write protect link

The write protect link P4 on the Master Repeat Card is factory
set to protected. Normally it is not necessary to change the link
from the factory set position, see the diagram above.
www.acornfiresecurity.com
3.15A(T)
mains fuse
P9
L
N N
0C
LC
01 L1 02 L2
P17
P16
FS4
DANGER
L
N
P8
DANGER
NO NOT
REMOVE
FS2
P5
NOT Write Protected
P4
P4
www.acornfiresecurity.com

Contrast and Emergency controls

RV1
SW1
8
7
SW1
6
Leave all
5
switches
4
in the OFF
3
position
2
1
OFF
ON
For keyswitch
application only.
Link is NOT USED
leave link fitted.
With Zone
indicators
Without Zone
indicators
Control buttons
Factory setting
is with link fitted
The display contrast is set using Pot RV1 on the DKC and is
factory set for optimum contrast.
The emergency control buttons must always be left in an
enabled state, with the control buttons link fitted.
WEEE Directive:
At the end of their useful life, the packaging,
product and batteries should be
disposed of via a suitable recycling centre.
Do not dispose of with your normal household waste.
Do not burn.
At the end of their useful life, the packaging,
product and batteries should be disposed of
via a suitable recycling centre and in
accordance with national or local legislation.
LCD Contrast adjust
Anti-Clockwise -
Lighter
RV1
Clockwise -
Darker
Display and
keyboard Card (DKC)
Inner door
P1
P6
1
2
3
4
Zones
17
18
19
20
Sound Alarms
Buttons
Verify
enabled
Reset
Buttons
Silence Alarms
disabled