Installation - Honeywell GENT VIG-RPT-72 Installation Manual

Vigilon repeat panel (en/bs)
Table of Contents

Advertisement

Data and installation

Installation

The Repeat Panel Set consists of:
Parts
j Backbox assembly
k Outer door assembly
l Inner door assembly
(with membrane labels for BS panel)
m 20 Way ribbon cable
n 40 Way ribbon cable
† Spares pack [Battery lead, Link wire (not used),
1 x 2A Fuse 20mm x 5mm QB,
2 x 3.15A Fuse 20mm x 5mm AB ceramic]
‡ Battery 12V 7Ahr
Fuses on the Master Repeat Card
Fuse
Rating
FS4
3.15A AS 20mm x 5mm
FS2
3.15A AS 20mm x 5mm
FS3
2A QB 20mm x 5mm
Back box mounting
3-off
Earth points
115mm
RESET
P2
SW3
P1
P7
FS3
USB
2A(QB)
Backbox
Floor level
Find the Repeat panel Back box  package and
a
remove the temporary cover.
Secure the back box to the wall with suitable
b
fixings. If the backbox is to be semi-flushed then
use the optional semi-flush surround.
Terminate the cable at the entry point leaving
c
400mm tail wire length.
&
If mains supply cable ends are not
required to be connected then ensure the ends are
insulated for safety.
2
www.acornfiresecurity.com
Qty
1
1
1
1
1
1
1
Cable entry points
4-off - Back and 4-off - Top
310mm
115mm
c L
P9
L
N N
0C LC
01 L1 02 L2
P17
P16
FS4
WRITE PROTECT
DANGER
P4
L
N
P8
DANGER
DO NOT
REMOVE
WARNING
Removal of
cover exposes
FS2
BUZZER
live parts.
DISABLE
DANGER
WD1
P14
P5
PB2
-
+
0V 24V
RS485
Fixing centres
4-off
www.acornfiresecurity.com
Vigilon Repeat panel (EN/BS)
Refit the temporary cover to protect the panel
d
until all building work is complete.
Aperture
Repeat panel
semi-flush surround
Flush
Repeat Panel
Surround
5mm diameter
fixing holes
Aperture Width: 320mm
Doors, Cables and Power up
The doors and cables can be installed after the
building work has finished.
Remove the protective cover from the backbox.
a
ƒ
b
Fit the inner door
to the panel enclosure
remembering to connect the earth lead from the
backbox to the inner door. Fit the outer moulded
door
to the backbox.
Wiring the panel:
c
&
Ensure the mains supply is completely
powered down before wiring the mains cable ends.
connect the mains cable to terminal block P9
on the Master Repeat Card.
fit battery lead
supplied in the spares to
connector P5 on Master Repeat Card.
connect the loop cables to terminal block P16
on the Master Repeat Card.
connect the 40 way ribbon cable
Master Repeat Card connector P2 and the
other end to Display Key Card on the top right
edge connector - P1.
connect the 20 way ribbon cable
Master Repeat Card connector P1 and the
other end to Display Key Card on the top right
edge connector - P6.
Power-up the panel by switching ON the mains
d
supply and then connect the battery leads to the
battery and note:
all the LEDs on the panel are lit for a short
duration and a power up message displayed.
the local buzzer sounds
the display reads: Main panel is off Line
the Fault and System Fault LEDs are lit.
4188-839_issue 8_07/14_pt1_EN/BS new Repeat_inst
Cross section of the wall to which
the panel is to be semi-flush mounted
Aperture depth should
not be less than: 59mm
Aperture Height:
380mm
to the
to the

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents