Ground Type
Earth ground (subbase and relay
module)
Signal Ground (KDM, Data ControlBus
Module™, Modbus™ Module)
Terminal No.
Abbreviation
G
Earth G
N
3
AL
4
FAN
5
L1
6
RT
7
LD2
8
PV1
9
MV
10
IGN
F(11)
12
Not Used
13
COM
14
MOD
15
Not Used
16
17
ES2
18
ES1
19
Not Used
20
LOS
21
PV2
22
SHTR
a
See Table 2.
b
2000 VA maximum connected load to 7800 SERIES Relay Module Assembly.
c
Total load current, excluding burner/boiler motor and firing rate outputs, cannot exceed 5A, 25A inrush.
d
Can also be 24 Vac, 3A at P.F. = 0.5.
e
220-240 Vac to 120 Vac, 10 VA minimum step-down transformer (not provided) required to drive shutter. Transformer
does not apply to UV flame sensor models C7061A1020, C7061A1079 and C7061F1003 (combined with R7861-series
flame amplifiers), which have internal selectable terminal block to connect 230V shutter output directly.
Table 2. Recommended Practice
1. Use to provide a connection between the subbase and the control panel of
the equipment. Earth ground must be capable of conducting enough cur-
rent to blow the 15A fuse (or breaker) in the event of an internal short cir-
cuit.
2. Use wide straps or brackets to provide minimum-length, maximum-sur-
face area ground conductors. If a leadwire must be used, use 14 AWG (2.5
2
mm
) copper wire.
3. Make sure that mechanically tightened joints along the ground path are
free of nonconductive coatings and protected against corrosion on mating
surfaces.
Use the shield of the signal wire to ground the device to the signal ground
terminal 3(c) of each device. Connect the shield at both ends of the daisy chain
to earth ground.
Table 3. EC7820A Terminal Ratings.
Description
a
Flame Sensor Ground
a
Earth Ground
Line Voltage Common (Neutral)
Alarm (Normally Open)
Burner/Blower Motor
Line Voltage Supply (L1)
Limits and Burner Control
Airflow Switch Input
Pilot Valve 1 (interrupted)
Main Fuel Valve
d
Ignition
Flame Signal
Firing Rate Common
Firing Rate Modulate
Control Voltage
Preignition Interlock Input
Low Fire Switch Input
Lockout Input
Pilot Valve 2 (Intermittent)
Shutter
5
EC7820A 7800 SERIES RELAY MODULES
Recommended Practice
Ratings
220/230/240 vac, 1A, 10 inrush for 5000 cycles.
220/230/240 Vac, 4A at P.F. = 0.5, 20A inrush.
220-240 Vac (+10%/-15%), 50/60 Hz (±10%).
220/230/240 Vac, 5A (maximum).
220/230/240 Vac, 1 mA.
220/230/240 Vac, 4A at PF = 0.5, 20A inrush.
220/230/240 Vac, 4A at PF = 0.5, 20A inrush.
220/230/240 Vac, 4A at PF = 0.2.
135 to 220 Vac, current limited.
220/230/240 Vac, 4A at PF = 0.5.
220/230/240 Vac, 4A at PF = 0.5.
220-240 Vac (+10%/-15%).
220/230/240 Vac, 1 mA.
220/230/240 Vac, 1 mA.
220/230/240 Vac, 1 mA.
220/230/240 Vac, 4A at PF = 0.5, 20A inrush.
220-240 Vac, 0.25A
c
c
c
d
d
c
32-00197—01