CDP Clock Exerciser

Load / No-Load Clock Exerciser
Allows the Generator to start and run unloaded or to
simulate a power failure, start Generator and run under
load. Can be configured by the end user for 1, 7, 14, 28,
or 365 day cycles.
 A total of 7 independent No Load exercise periods
(up to 10 hours each) can be programmed for each
of the daily, weekly, 14-day, and 28-day exercisers.
 A total of 12 independent No Load exercise periods
(up to 10 hours) can be programmed for the
365-day Exerciser.
How to Configure (CFG) the Exerciser
1. Beginning from the S1 OK screen, press MORE
then CFG.
2. Press MORE to scroll to CONFIG CLOCK
EXERCISER screen.
3. The third line of the CONFG CLOCK EXERCISER
will show either DAILY, WEEKLY, 14 DAY, 28 DAY,
365 DAY or OFF.
4. If the third line of the CONFG CLOCK EXERCISER
shows DAILY, WEEKLY, 14 DAY, 28 DAY, or 365 DAY
as desired, press MORE repeatedly to BACK.
Press ESC then proceed to the SET menu to
set the EXERCISER.
5. If the third line of the CONFG CLOCK EXERCISER
shows OFF, continue.
6. Press SEL.
7. Enter ACCESS code located on white label on
the back of the controller.
8. Press UP or DOWN to select DAILY, WEEKLY,
14 DAY, 28 DAY, or 365 DAY as desired.
9. Press SAVE.
10. Press MORE repeatedly to BACK then ESC
to S1 OK screen.
How to set (SET) the DAILY Exerciser
1. Beginning from the S1 OK screen, press MORE
then SET.
2. Press MORE repeatedly until SET EXERCISER
screen.
3. Press SEL.
4. Enter ACCESS code located on white label
on the back of the controller.
5. Press SEL
Indicates # of
Exercise Periods
Indicates type of Exerciser
DAILY, WEEKLY, 14-DAY,
28-DAY or 365-DAY
Indicates Exerciser start:
Time for DAILY Exerciser
Time & Day for WEEKLY Exerciser
Time, Date & Month for 14-DAY,
28-DAY and 365-DAY Exerciser
(24 Hour System)
GE Zenith Controls
6. Cursor is indicated as a line under character to
7. Press BACK when complete.
8. Press MORE repeatedly until SET USER SETUP.
How to Bypass (Cancel) an exercise during
an exercise cycle
1) Press BPASS
2) Allow the controller to complete the Engine
If the CD Exerciser is configured or Set for a No-Load
Exercise. Or allow the controller to complete retransfer
to Source 1. If the CD Exerciser is configured for a
Load Exerciser
How to Bypass the next exercise event and Keep
the rest of scheduled events unchanged
1) Press TEST
2) Press MORE
3) Press BYPASS EXER
To re-institute the next exercise event back,
press CANCL BPASS
How to check the next exercise event
1) From S1 OK screen, press MORE three times.
2) The unit will display the PLANT EXERCISER NEXT
3) Press ESC to S1 OK Screen.
Notes:
 In the S1 OK screen, an (*E*) appears in the upper
 For Load Exerciser, actual exercise period
 A value greater than zero must be entered in the
 The Exercise cycle will be repeated on a regular
Cursor
#1
SET
EXERC I SER
v
BACK
^
Up and Down
Use to change values.
To previous field
or to exit screen.
ZTS / ZTSD Operation and Maintenance Manual (71R-3000)
be changed. Change values with up and down keys.
Press SAVE after each entry to save value and to
move to the next value to be changed.
Press BACK then ESC to the S1 OK screen.
cool down cycle.
event in DAYS, HOURS, and MINUTES
right hand corner of LCD screen when exercise
is impending.
(ATS in S2 position)= CDT (Exerciser)
timing period +T (S1 Stable Timer) timing period.
Exerciser duration field to be accepted as a valid
exercise period.
basis as programmed and initiated in the SET menu
depending on what Exerciser was configured
(selected) in the CFG menu.
NL
0 0: 0 0
S AVE
To save value and to
move cursor to next
field to be changed.
Load No-Load (CDP)
Exercise Indicator
Exercise duration for this
event in hours and minutes
up to 10 hours per event
Figure 9
15