9.5.2 Detector Inhibit
The detector can be placed in an inhibit state for maintenance purposes. This will have the effect of
suppressing the alarms, the current loop will be forced to the level that has been set for inhibit and the visual
indicator will light yellow.
To do so, swipe the control in the top-right of the screen to
the right.
A message will be displayed to inform you that this will
suppress alarms. Tap OK to continue or Cancel to return to
the present condition.
CAUTION
Fault relay will be triggered when user performs
Inhibit operation.
To return to Active mode, swipe the control in the top-right
of the screen to the left and acknowledge the message.
Note
The Searchzone Sonik detector will remain in Inhibit mode.
It is possible to set a time out so that the detector returns to
Active mode after a preset amount of time. Refer to section
9.9 Detector Settings for more information.
CAUTION
The default inhibit timeout is set 0 and the detector will remain in inhibit unless end
user manually clears the inhibit condition. Changing the inhibit timeout settings (to, for
example, 10 minutes) and saving the changes will NOT affect the current session. The
change in inhibit timeout will be made in next session when end user puts the detector
into inhibit.