Appendix - Honeywell C7232A Product Data

Sensor and controller, carbon dioxide sensor
Table of Contents

Advertisement

APPENDIX

IMPORTANT
This page is only for models with date code prior to 0309.
Pre 0309 Date Code Jumper Settings
Input Signal
The C7232 Sensors have an adjustable range. These ranges
are determined by the SW2 and OUT1 jumper settings (see
Table 6).
NOTE: When choosing analog output, be sure to set the
SW1 jumper to the On position.
Table 6. CO
Range Jumper Settings for models
2
with date code prior to 0309.
Jumper SW1
a
Jumper
Setting
On
AN1
X
b
OUT1
X
a
AN2
X
b
Relay Switching
a
Setting when shipped from the factory.
b
OUT1 jumper setting does not affect the Relay Switching.
c
The analog output will not work properly when SW1 is Off.
d
When the level reaches this value, the contacts close; when the
level drops 100 ppm below this value, the contacts open.
Output Signal
The output signal can be adjusted for 0/2-10Vdc or 0/4-20mA
(see Table 7).
Jumper SW2
a
Off
On
Off
0 to 1000
0 to 2000
c
500 to 1500
500 to 2000
c
d
d
800
1200
X
d
1000
C7232A,B SENSOR AND CONTROLLER
Table 7. Output Signal Jumper Settings for models
with date code prior to 0309.
AN1 and AN2 (set
both the same)
Voltage
Current
NOTES:
On duct models with date code prior to 0309, remove
the screw holding the board in place to view jumper
settings on reverse. (See Fig. 8.)
The CO
2
independent of each other. 0-100% and 20-100% are
simply markings for the OUT jumper settings on the
sensor (to differentiate between the two voltage and the
two current ranges) and do not refer to or alter the ppm
range chosen.
SW2SW1 OUT
Fig. 8. C7232 default jumper settings for models
with date code prior to 0309.
7
OUT
0-100%
0-10Vdc
2-10Vdc
0-20 mA
4-20 mA
settings and the output signal settings are
AN2
AN1
OUT1
Select
20-100%
M20494
63-2571—4

Advertisement

Table of Contents
loading

This manual is also suitable for:

C7232b

Table of Contents