7800 SERIES RELAY MODULES
Fault Code
Fault 51
Flame signal value is too high
*Flame Too Strong*
to be valid.
Fault 52
Pilot Valve 2 (terminal 21) was
*Call Service*
off when it should be on.
Fault 53
Lockout Input fault
*Lockout Switch*
(EC/RM7810, 7820, 7830,
7850 only).
Fault 54
Combustion pressure switch
*Comb. Pressure*
fault (Fulton pulse only).
Fault 55
Purge fan switch is on when it
*Purge Fan Sw. On*
should be off (Fulton pulse
only).
Fault 56
Block intake fault
*Block Intake*
(Fulton pulse only).
Fault 57
Purge Fan Switch is off when
*Purge Fan Sw. Off*
it should be on (Fulton pulse
only).
Faults 58 - 66
Unused faults
*Call Service*
Fault 67
L1 and L2
*AC Phase*
miswired/exchanged
(EC/RM7810, 7820, 7830,
7850 only).
65-0229—1
Table 3. Hold and Fault Message Summary (continued).
System Failure
1.
2.
3.
4.
5.
6.
7.
8.
1.
2.
3.
1.
2.
3.
4.
1.
2.
3.
4.
5.
1.
2.
3.
4.
1.
2.
3.
4.
5.
1.
2.
3.
1.
Recommended Troubleshooting
Make sure that flame detector and flame amplifier are
compatible.
Remove the flame amplifier and inspect the connections. Reset
the flame amplifier.
Reset and sequence the relay module.
Check the flame detector sighting position, reset and cycle.
Verify that no ignition noise is present in the F lead due to wire
routing.
Measure the flame strength. Verify it meets specifications. If
not, refer to the flame amplifier and/or flame detector checkout
procedures.
If the code reappears, replace the flame amplifier and/or the
flame detector.
If the fault persists, replace the relay module.
Inspect terminal 21 and connections. Make sure that the valve
is operating properly.
Reset and sequence the relay module.
If the fault persists, replace the relay module.
Check wiring; correct any errors.
Inspect the Lockout Switch to make sure it is working
properly.
Reset and sequence the relay module. During STANDBY or
PREPURGE, measure the voltage between terminal 20 and G
(ground). Supply voltage should be present. If not, the
lockout switch is defective and needs replacing.
If the fault persists, replace the relay module.
Check wiring; correct any errors.
Inspect the Combustion Pressure Switch to make sure it is
working correctly.
Reset and sequence the relay module.
During STANDBY or PREPURGE, measure the voltage
between terminal 20 and G (ground). Supply voltage should
be present. If not, the Combustion Pressure Switch is
defective and needs replacing.
If the fault persists, replace the relay module.
Check wiring; correct any errors.
Inspect the Purge Fan Switch terminal 18 and its connections.
Make sure the switch is working correctly and is not jumpered
or welded.
Reset and sequence the relay module.
If the fault persists, replace the relay module.
Check wiring; correct any errors.
Inspect the Block Intake Switch and make sure it is working
properly.
Reset and sequence the relay module.
During PREPURGE, measure the voltage between terminal 7
and G (ground). Supply voltage should be present. If not, the
Block Intake Switch is defective and needs replacing.
If the fault persists, replace the relay module.
Inspect the Prepurge Fan Switch terminal 18 and the
connections. Make sure the switch is working properly.
Reset and sequence the relay module.
If the fault persists, replace the relay module.
Check L1 and L2 for proper line phasing.