UV100E ULTRAVIOLET SYSTEMS
10. For Air Treatment Systems, wait ten minutes for the
airflow sensor to calibrate. During this time, the furnace
fan must remain off.
NOTE: Failure to wait ten minutes for the airflow sensor to
calibrate before powering the system fan causes the
airflow sensor to incorrectly calibrate and the device
to incorrectly function. If this occurs, remove power to
the furnace or turn off the system fan, wait ten
minutes, and then resume normal fan operation.
11. Verify that ultraviolet lamp is operating by viewing only
through the lamp light indicator on the lamp handle.
Never look directly at your bulbs while illuminated.
12. Reconnect power to your heating and cooling system.
CAUTION
UV Lamp Burn Hazard.
Harmful to bare skin.
Can cause severe burns.
Disconnect power 15 minutes before removing
ultraviolet bulb(s).
Bulb Replacement
Replacement of the bulb in your ultraviolet lamp when the LED
is solidly lighted is required to maintain effectiveness.
1. Obtain the correct replacement bulb for your unit. See
Table 1.
Table 1. Select a Replacement Bulb/Handle Assembly
or Replacement Bulb.
Unit Description
UV100E1043
Air Treatment System
UV100E2009
Air Treatment System
UV100E3007
Surface Treatment
System
2. Disconnect power to your heating and cooling system.
3. Unplug or turn off power to your UV System and allow
the lamp to cool for at least 15 minutes.
4. Rotate the lamp handle counterclockwise and gently pull
the lamp handle to remove the bulb(s). See Fig. 11.
5. If you have a SnapLamp™ handle, follow steps 5 and 6;
otherwise, proceed to step 7. Grasp the SnapLamp™
handle in one hand and the lamp glass in the other and
pull straight apart. See Fig. 16.
68-0262—5
Replacement
SnapLamp™
Bulb/Handle
Replacement
Assembly
Bulb
UC100E1006
UC18W1004
UC100E1030
UC36W1006
(two required)
(two required)
UC100E1030
UC36W1006
Fig. 16. Disconnect lamp glass from SnapLamp™ handle.
6. Insert the new lamp glass into the SnapLamp™ handle
by aligning the notch and pushing straight together. See
Fig. 17.
Fig. 17. Replace lamp glass in SnapLamp™ handle.
7. Insert the lamp handle into the base with the lamp light
indicator at the eleven o'clock position. Continue pushing
and gently rotating counterclockwise until the lamp
handle inserts fully into the base. See Fig 4.
8. Rotate the lamp clockwise until it snaps into place with
the lamp light indicator aligned with the raised button on
the unit cover. See Fig. 6.
9. Reconnect power to your UV System.
10. For UV Air Treatment Systems, wait ten minutes for the
airflow sensor to calibrate. During this time, the furnace
fan must remain off.
NOTE: Failure to wait ten minutes for the airflow sensor to
calibrate before powering the system fan causes the
airflow sensor to incorrectly calibrate and the device
to incorrectly function. If this occurs, remove power to
the furnace or turn off the system fan, wait ten
minutes, and then resume normal fan operation.
WARNING
UV Light Hazard.
Harmful to bare skin and eyes.
Can cause temporary or permanent loss of vision.
Never look at bulbs while illuminated.
View illumination only through lamp light indicator
located on lamp handle.
To prevent exposure to ultraviolet light, disconnect
power to ultraviolet system before servicing any part of
heating and air conditioning system.
11. Verify that your ultraviolet lamp is operating by viewing
only through the lamp light indicator on the lamp handle.
Never look directly at your bulb while it is illuminated.
12. Reconnect power to your heating and cooling system.
13. Press and hold the reset button for five seconds to reset
the internal timers.
10
M22851
M22853