d. Mount the case back to the wall using two flat head dry-wall
screws, anchoring it to a wall stud or other solid wood material.
e. Reinstall the PC board into the case back, position the board onto
the two retaining studs on one side of the case back and snap the
board into place. The hold-down tab must mate with the
corresponding cutout in the case back after case back is installed.
6. Set the DIP switch (after the control panel has enrolled the
transmitter loops) for the desired primary loop characteristics, as
described in the Primary Loop Options Table.
NOTES:
• The DIP switch may be set by the installer only. It is not a user
function.
• Due to FCC regulation 15.231(a)(4), this switch may not be set to
ON unless loop 1 is used to indicate a type of emergency
involving fire, security, or safety of life.
PRIMARY LOOP OPTIONS TABLE
SWITCH
DIP SWITCH POSITION
SET TO
REPEATING TRANSMISSION
(every 4 sec.)
ON
UPON PRIMARY LOOP 1 FAULT
Use for high priority alarm, such as fire.
SINGLE TRANSMISSION
OFF
PER PRIMARY LOOP CHANGE-OF-STATE
Notes: a. In order for the control panel to enroll the transmitter, DIP
switch 1 must be set to OFF (see Figure 3).
b. The Auxiliary loops are not affected by the DIP switch
settings.
3
Wiring Connections
Connect the loop wiring to the unit's terminals before installing the
battery (see Figure 3).
NOTES:
a. Primary loop 1 is a supervised loop and must have an end-of-line
(EOL) resistor (470K ohms, supplied) placed across the last sensor.
Additionally, for Primary loop 1, a contact device may not be installed
more than 20 feet from the transmitter.
b. For UL household burglary and fire installations, the loop 3 contact
device (if used) may not be more than 3 feet from the transmitter.
4
Battery Installation/Replacement
1. Remove the transmitter's cover as described in Mounting Step 2.
2. Observe correct polarity and insert the battery provided into the
battery holder (see Figure 3). Take care not to bend the antenna.
Note: Replace battery only with: Duracell DL123A, DL123,
Panasonic CR123A or ADEMCO 466.
Risk of fire, explosion, and burns. Do not recharge,
disassemble, heat above 212°F (100°C), or incinerate.
Dispose of used batteries promptly. Keep away from
children.
3. To replace the cover, engage the hooks along the top edge and
snap shut. Install cover locking screws when required for regulatory
agencies.
ENROLLMENT NOTE: Wait 30 seconds after battery installation
before enrolling transmitter.
Ê800-18448nŠ
800-18448 5/14 Rev. B
5
Testing
Regular maintenance and inspection (at least annually) by the installer
are vital to continuous satisfactory operation of any alarm system. The
installer should instruct the user to test the system frequently (at least
weekly) to insure the system's operation at all times, as well as offer a
regular maintenance program to the user. The user should also be
acquainted with proper operation and limitations of the entire alarm
system. For testing procedures, refer to the User Guide or Installation
and Setup Guide for the system control panel.
UL Requirement
1. If using a compatible commercial control panel (ex. VISTA Turbo
series) and programming the 5817CBXT as an Entry/Exit zone, you
must enroll the tamper loop (loop 4) as a separate zone,
programmed for 24-hour response (e.g., Zone type 5  Trouble-by-
day/Alarm-by-night).
2. For UL Commercial Burglary installations, this transmitter must be
used in conjunction with the 5881ENHC RF Receiver.
Specifications
U L
For dry, indoor use only. Do not install in air-handling
spaces.
Dimensions: 1-9/16"W x 3-1/2"H x 1-3/16"D (40mm x 89mm x 30mm)
Battery: 3V Lithium (see BATTERY INSTALLATION/REPLACEMENT).
Signal Level: To determine ambient noise level and signal strength,
refer to compatible receiver Installation and Setup Guide.
NFPA-72 Compliant.
UL Listings:
Commercial Fire.......UL864
Household Fire.........UL985
Household Burg........UL1023
Commercial Burg......UL365, UL609, UL1076, UL1610
For Limitations of the entire alarm system, refer to the control panel's
installation guide for the receiver/control with which this device is used.
FEDERAL COMMUNICATIONS COMMISSION STATEMENT
The user shall not make any changes or modifications to the
equipment unless authorized by the Installation Instructions or User's
Manual. Unauthorized changes or modifications could void the user's
authority to operate the equipment.
FCC / IC STATEMENT
This device complies with Part 15 of the FCC Rules, and RSS 210 of
IC. Operation is subject to the following two conditions:
(1) This device may not cause harmful interference.
(2) This device must accept any interference received, including
interference that may cause undesired operation.
Cet appareil est conforme à la partie 15 des règles de la FCC & de
RSS 210 des Industries Canada. Son fonctionnement est soumis aux
conditions suivantes:
(1) Cet appareil ne doit pas causer d' interférences nuisibles.
(2) Cet appareil doit accepter toute interférence reçue y compris les
interférences causant une réception indésirable.
WARRANTY Go to:
http://www.security.honeywell.com/hsc/resources/wa/
DOCUMENTATION AND ONLINE SUPPORT Go to:
http://www.security.honeywell.com/hsc/resources/MyWebTech/
2 Corporate Center Drive, Suite 100
P.O. Box 9040, Melville, NY 11747
Copyright  2014
Honeywell International Inc.
www.honeywell.com/security