GE PACSystems RX3i User Manual page 133

Profinet io-controller
Hide thumbs Also See for PACSystems RX3i:
Table of Contents

Advertisement

Chapter 5. Diagnostics
Group/
Category/
Description
Type/
Descriptor
9-71-0-0
Duplicate IP
Address detected
on the network.
9-72-0-0
Duplicate IP
Address conflict
resolved.
28-37-0-0
Unexpected
PROFINET Alarm
received.
28-38-0-0
Manufacturer
specific Diagnosis
Appears PROFINET
Alarm received.
122
PACSystems* RX3i & RSTi-EP PROFINET IO-Controller User Manual
Cause
PROFINET Controller has
detected a duplicate IP
Address on the network.
The location associated
with the fault will indicate
whether the duplication is
with the PROFINET
Controller itself, or with a
configured PROFINET
Device.
PROFINET Controller has
detected that a previously
duplicated IP Address
conflict has been resolved.
The location associated
with the fault will indicate
whether the duplication
was with the PROFINET
Controller itself, or with a
configured PROFINET
Device.
The PROFINET Controller
has received a PROFINET
alarm that is unexpected.
Possible causes could
include a malformed
PROFINET Alarm packet or
an Alarm for a PROFINET
sub-module that is not
configured.
A PROFINET Alarm has
been received indicating
that a manufacturer
specific diagnostic
condition has been
detected on the PROFINET
device.
Recommended
Correction
Either remove the device on the
network that has the duplicate IP
Address, or assign a new IP Address
to either the PROFINET Controller or
the conflicting device.
Note: The Fault Extra Data displays
the MAC addresses of the conflicting
devices in the MAC 1 field (bytes 8–
13) and the MAC 2 field (bytes 14–19).
If the PROFINET Controller is one of
the devices with a conflicting IP
Address, MAC 1 will be 0. This data is
stored in Big Endian (most significant
byte in lowest address) format.
Also, if the conflict is between
PROFINET devices on the network,
the DCP Tool can be used to help find
the conflict. Sorting by IP Address
within the tool may make it easier to
identify the duplicates.
None.
Consult Device manufacturer
documentation.
Note: Alarm details are provided in
the Fault Extra Data
Consult Device manufacturer
documentation.
Note: Alarm details are provided in
the Fault Extra Data
GFK-2571N