Panasonic Eco Solutions Nordic AB
MEW01457
28.7
Action
"Access"
Scroll to menu A6
"A"
"A"
or
"1", "A"
"A"
"Return"
Rev: -
Display current consumption COM-/BS4-
loop (H5/A6)
The resolution is not very high, i.e. the displayed values give only a
rough idea of the current consumption.
The current consumption (an average value) for each COM loop and
110
BS4 loop
can be displayed.
NOTE! No or very small current consumption can not be presented
correctly / precisely.
Text in display
Display current consumption on
COM-/BS4-loop
Select type of loop: 0 (0=COM, 1=BS4)
Display current consumption on
COM-loop: 0, CU: 00
Display current consumption on BS4-
loop: 0, board: 0, CU: 00
Wait......
No reply from control unit.....
Current consumption on COM-loop: 0
control unit: 00 is xxxx mA
Current consumption on BS4-loop: 0,
board: 0, control unit: 00 is xxx mA
Display current consumption on
COM-/BS4-loop
110
An Autronica interface board 1584 is required in the control unit.
Operating Instructions Fire alarm system EBL512, V2.7.x
ACCEPT? A6
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT? A6
132
Comments
According to chapter
"Access code for service
(H5)", see page 126.
Select type of loop. Press
"A" to accept.
Write loop number, (board
number; 0-3) and control
unit number. Press "A" to
accept.
If the control unit don't
exist or don't answer, this
message will be shown.
The current consumption
accuracy is ±5 mA.
Scroll or press "Return" to
H5. Scroll or press
"Return" to log off.