Grounding the Cisco Nexus 7004 Chassis
Figure 2-3
1
NRTL listed 45-degree grounding lug
Use the crimping tool to crimp the lug to the grounding wire. Verify that the ground wire is securely
Step 3
attached to the ground lug by attempting to pull the wire out of the crimped lug.
Remove the adhesive label from the system grounding pad on the chassis, secure the grounding wire lug
Step 4
to the grounding pad with two M4 screws, and tighten the screws to 11.5 to 15 in-lb (1.3 to 1.7 N·m).
Callout 1 in
Be sure that the grounding lug and wire do not block the ESD port by positioning the lug and wire
Note
connection above the grounding port.
Figure 2-4
1
2
1
Grounding pad
Cisco Nexus 7000 Series Hardware Installation and Reference Guide
2-10
Inserting the Grounding Wire in the Grounding Lug
Figure 2-4
shows the location of the grounding pad on the front side of the chassis.
Grounding Pad and ESD Port Locations on the Cisco Nexus 7004 Chassis
Chapter 2
Installing a Cisco Nexus 7004 Chassis
2
Grounding cable with 0.75 in. (19 mm) of insulation
stripped from the end
2
ESD port
OL-23069-07