S05, S10, S20 SERIES SPRING RETURN DIRECT COUPLED ACTUATORS
1
24 VAC
2
1
LINE VOLTAGE POWER SUPPLY.
PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
2
24 VDC SUPPLY ACCEPTABLE.
3
SET SWITCH TO MODULATING.
ENSURE PROPER GROUNDING OF ACTUATOR CASE.
4
Fig. 16. Wiring for two-wire SPST on/off control.
1
24 VAC
2
1
LINE VOLTAGE POWER SUPPLY.
PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
2
24 VDC SUPPLY ACCEPTABLE.
3
SET SWITCH TO FLOATING.
ENSURE PROPER GROUNDING OF ACTUATOR CASE.
4
Fig. 17. Wiring for floating control.
1
24 VAC
2
0/2 TO 10 VDC
PROPORTIONING
CONTROLLER
+
FEEDBACK
1
LINE VOLTAGE POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.
2
24 VDC SUPPLY ACCEPTABLE.
3
SET SWITCH TO MODULATING.
4
ENSURE PROPER GROUNDING OF ACTUATOR CASE.
Fig. 18. Wiring for 0/2-10 Vdc proportioning controllers.
63-2607—08
ACTUATOR
1
SPST
V
4
2
3
OR +
OR N/A
4
5
FEEDBACK
2-10 VDC
10-2 VDC
0-10 VDC
3
10-0 VDC
Fltg, fwd
Fltg, rev
M22291A
ACTUATOR
1
V
4
2
3
OR +
OR N/A
4
FEEDBACK
5
2-10 VDC
10-2 VDC
0-10 VDC
3
10-0 VDC
Fltg, fwd
Fltg, rev
M19573B
ACTUATOR
1
V
4
2
3
OR +
OR N/A
4
FEEDBACK
5
2-10 VDC
10-2 VDC
0-10 VDC
3
10-0 VDC
Fltg, fwd
Fltg, rev
M19574B
1
24 VAC
4 TO 20 mA
PROPORTIONING
CONTROLLER
+
FEEDBACK
1
LINE VOLTAGE POWER SUPPLY.
PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
2
24 VDC SUPPLY ACCEPTABLE.
3
SET SWITCH TO MODULATING.
4
ENSURE PROPER GROUNDING OF ACTUATOR CASE.
Fig. 19. Wiring for 4-20 mA proportioning controllers.
1
24 VAC
CONTROLLER
HOT
COM
1
LINE VOLTAGE POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.
2
SET SWITCH TO FLOATING.
ENSURE PROPER GROUNDING OF ACTUATOR CASE.
3
Fig. 20. Wiring for high side (triac source) floating control.
1
24 VAC
CONTROLLER
HOT
COM
1
LINE VOLTAGE POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.
2
SET SWITCH TO FLOATING.
ENSURE PROPER GROUNDING OF ACTUATOR CASE.
3
Fig. 21. Wiring for low side (triac sink) floating control.
10
ACTUATOR
1
2
4
2
3
490 TO 510
4
OHMS,
1/2 W
5
FEEDBACK
MINIMUM
3
ACTUATOR
1
3
2
3
OR +
OR N/A
4
5
FEEDBACK
2
ACTUATOR
1
3
2
3
4
FEEDBACK
5
2
V
OR +
OR N/A
2-10 VDC
10-2 VDC
0-10 VDC
10-0 VDC
Fltg, fwd
Fltg, rev
M22282B
V
2-10 VDC
10-2 VDC
0-10 VDC
10-0 VDC
Fltg, fwd
Fltg, rev
M22283A
V
OR +
OR N/A
2-10 VDC
10-2 VDC
0-10 VDC
10-0 VDC
Fltg, fwd
Fltg, rev
M22284A