10.3.24 Password
Operations: Write
Meaning:
If properly setted, gives the access to configuration.
10.3.25 Actual power
Operations: Read
10.3.26 Feed-Back
Operations: Read
10.3.27 Soft start time
Operations: Read/Write
OUT
Soft Start Time
Par 125H x 5msec
10.3.28 Delay time HB
Operations: Read/Write
Meaning:
It's a value in point (0 – 255, 0 – FF Hex).
Each step is 50msec.
It represents a delay time before to have HB alarm active.
When is used with soft start, this time must be longer than soft start time.
Par126H x 50msec > Par125H x 5msec
10.3.29 % HB
Operations: Read/Write
Meaning:
It corresponds to a value in point (0-255, 0-FF Hex)
The maximum load current (100%) minus this parameter (x%) is the value establishing the HB
current set point.
Example:
Load current
Parameter 124H
Parameter 2 will be setted at 8A.
www.honeywell.com/imc
CD3200 up to110A
Meaning:
It's corresponds to the value in points (0 – 255, 0 – FF Hex).
Each step is 5msec .
The unit starts in phase angle mode with a ramp starting from
zero up to full voltage in a presetted and Adjustable time.
The time is setted by this parameter.
Time
= 10A
= 20%
51 Dec
46
User's Manual ver. 2.0
33 Hex
Parameter 123
Parameter 124