10.3.7 Output Power
Command from controller
Operations: Read
Meaning:
It rapresents a value in points (0-255, 0-FF Hex) and it's the power demand in % of controller.
Example:
0%
= 0
50%
= 128
100%
= 255
Command via RS485
Operations: Read/Write
Meaning:
It's a value in points (0-255, 0-FF Hex).
It's power set point setted in thirst buffer.
Example:
0%
= 0
50%
= 128
100%
= 255
10.3.8 Output Power Ramping (0 – FFH)
Operations: Read
10.3.9 Power adjust
Operations: Read/Write
Meaning:
It's a value in points (0-255, 0-FF Hex).
It's a scaling factor of power demand.
Example 1:
0%
= 0
50%
= 128
100% = 255
Example 2:
Output Power: 100
Power Limit: 100%
-> Real power: 100
Output Power: 100
Power Limit: 50%
-> Real power: 50
Output Power: 80
Power Limit: 50%
-> Real power : 40