Download Print this page

Honeywell 900CS10-00 Installation Manual page 13

Hc900 control station

Advertisement

Specifications – apply to all models unless specified.
Environmental
Safety
Electromagnetic
Compatibility
51-52-33-157 Rev. 6
Operating Temperature Range: 0 to 50 °C (32 to 122 F)
Storage Temperature Range: -20 to 70 °C (-4 to 158 °F)
Operating and Storage Humidity: 80% maximum relative humidity (non-condensing) from
0 to 50°C.
Vibration According to IEC 68-2-6: 5 to 150 Hz, in X, Y, Z direction for 1.5 hours, 2 g.
Shock According to IEC 68-2-27: Operational 35 g, 9 msec in 3 directions.
Type 4X Indoor use only Enclosure rating (face only), UL50.
IP66 Enclosure rating (face only), IEC529.
Altitude: Up to 2000 meters.
EN 61010-1 – 2001. CE Mark requirements for General Purpose (Ordinary Location)
Safety.
ANSI/UL 61010-1 – 2005, Second Edition. General Purpose (Ordinary Location) Safety.
UL evaluated to CSA C22.2 No. 61010-1-2004- Second Edition. General Purpose
(Ordinary Location) Safety.
UL, CSA and FM Class I, Div 2 Groups A,B,C and D
IEC61326 - 2005 CE Mark EMC requirements for electrical equipment for measurement,
control and laboratory use.
Immunity to Industrial Locations:
ESD
IEC 61000-4-2
EM field
IEC 61000-4-3
Electrical Fast
IEC 61000-4-4
Transient/Burst
Surge
IEC 61000-4-5
Conducted RF
IEC 61000-4-6
Magnetic field
IEC 61000-4-8
Emissions:
Emissions
EN 55011
(CISPR11)
Criterion A
4kV contact discharge
8kV air discharge
Criterion A
10 V/m (80 MHz to 1 GHz)
3 V/m (1.4 GHz to 2 GHz)
1 V/m (2.0 GHz to 2.7 GHz)
Criterion A
2kV power
1kV I/O signal/control,
including functional earth lines
Criterion B
1kV L-L, 2kV L-Gnd power
1kV I/O signal/control,
including functional earth lines
Criterion A
3Vrms Power and all I/O
Criterion A
30A/m
Class A
Page 13 of 14